CONFIGURE will display the interrogation (polling) list.
CONFIGURE POSITION shows the next position to be defined.
CONFIGURE POSITION # sets the position to be defined next.
CONFIGURE ID #-# DISPLAY #-# tells the system which ID
numbers and DISPLAY numbers to poll.
NOTE:
You can duplicate addresses using the CONFIGURE ID #-#
DISPLAY #-# command. Verify addresses by displaying the
polling list with the CONFIGURE command. T/Shell uploads
will not accept duplicate addresses.
CONFIGURE POSITION # SKIP # reserves (leaves undefined) a
number of displays. For example, POS 5 SKIP 10 means config-
ure 5, skip positions 6 through 9, and configure 10 next.
CONFIGURE CLEAR ALL empties the configuration database.
CONFIGURE CLEAR # clears that position.
C0NFIG, or CONF, or CON may be substituted for CONFIG-
URE.
POSN or POS may be substituted for POSITION.
DISP may be substituted for DISPLAY.
CLR may be substituted for CLEAR.
The symbol # is an individual device. The possible range of
numbers for ID is 1 to 32. The possible range of numbers for
POSITION is from 1 to 128 for the 46062-03 and 1 to 512 for the
46062-02. The possible range of numbers for DISPLAY is from
1 to 64.
It is important to understand the different ways in which
different DCPF devices report their alarm displays. Most DCPF
devices that the Status Monitor will poll report up to 32 displays
of alarms for each address entered in step 1. Other DCPF
devices can report up to 64 displays at one address. The Status
Monitor is capable of polling both.
For example, the MAP -40 can report 64 displays of alarms but
to do so must report them using two addresses: displays 1 to 32
as the first address and displays 33 to 64 as the second. In this
situation, configure the Status Monitor to poll the first 32
displays at the first address and as displays 1-32. The second
group of 32 displays is configured to be polled at the second
address but as displays 1-32 also. Note that while the displays
are numbered 33-64 on the MAP -40, they are reported as
displays 1-32 at the second address.
Another DCPF device, the MAP -41, is capable of reporting up to
128 displays of alarm information using two addresses. Dis-
plays 1-64 are reported at the first address and displays 65-128
at the second. Configure the Status Monitor to poll displays