![Dantel 46062-02 Installation & Operation Manual Download Page 34](http://html1.mh-extra.com/html/dantel/46062-02/46062-02_installation-and-operation-manual_3459426034.webp)
P
AGE
34
46062-0299 <90-00016>
1-64 at the first address and displays 1-64 at the second address.
Note that while the displays are numbered 65-128 at the
MAP -41, they are reported as displays 1-64 at the second
address.
Refer to the Operation Manual specific to the device you are
polling for details on that devices capabilities.
Input Example:
CON
Output Response:
POS 1 ID 1 DISP 5
POS 3 ID 1 DISP 7
POS 4 ID 1 DISP 32
POS 5 ID 3 DISP 1
POS 66 ID 1 DISP 66
OK
NOTE:
The command CON displays the interrogation (polling) list.
The sample list above shows that the first device to be polled
(position 1) will be MAP address 1, display 5. Position 2 is not
being used, so the next device to be polled will be position 3,
which is MAP address 1, display 7. Devices are polled in the
order that they are listed in the position list.
There are 64 possible displays of alarm information per
address. Displays 65, 66, and 67 (plus displays 68 through 73
if the expanded memory option has been installed) are
generated internal to the GPP and are used to report device
communication failures within the alarm system. See
OUTPUT MESSAGES.
C
ONTROL
Purpose:
Authorizes the use of control points for alarm annunciators.
Format:
CONTROL ON
CONTROL OFF
PRINTER SYNTAX