P
AGE
24
46062-0299 <90-00016>
Set ID 1 Disp 8 Pnt 4 Minor
Defines the alarm at point 4 as a local and minor (level C) alarm.
Set ID 1 Disp 8 Pnt 5 Global
Defines the alarm at point 5 as a global alarm. The GPP as-
sumes that any alarm not defined as level A, B or C is a level D
alarm, so there is no need to define point 5 as a level D alarm.
Desc ID 1 Disp 8 Pnt 1
15:36:09 11-14-96 ENTER TEXT...
Lets you enter a text message describing the alarm point. Do not
exceed 32 characters.
Desc ID 1 Disp 8 Pnt 2
15:36:09 11-14-96 ENTER TEXT...
Lets you enter a text message describing the alarm point. Do not
exceed 32 characters.
Desc ID 1 Disp 8 Pnt 3
15:36:09 11-14-96 ENTER TEXT...
Lets you enter a text message describing the alarm point. Do not
exceed 32 characters.
Desc ID 1 Disp 8 Pnt 4
15:36:09 11-14-96 ENTER TEXT...
Lets you enter a text message describing the alarm point. Do not
exceed 32 characters.
This sample defined four of the 192 points in the three interro-
gated (polled) displays. The other 188 points default to local
status (level D) alarms.
Sys
The system is configured. The GPP automatically polls MAP 1,
displays 8, 9 and 10. The GPP displays any of the 192 alarms
within displays that experience a change of state. The SYS
command displays any active alarms.
PRINTER SYNTAX