![Dantel 46062-02 Installation & Operation Manual Download Page 54](http://html1.mh-extra.com/html/dantel/46062-02/46062-02_installation-and-operation-manual_3459426054.webp)
P
AGE
54
46062-0299 <90-00016>
R
EMOTE
B
AUD
Purpose:
Displays the baud of the data port or changes the baud between
1200 and 9600.
Format:
REMOTE BAUD
REMOTE BAUD 1200
REMOTE BAUD 9600
Remarks:
REMOTE BAUD displays the baud of the data port.
REMOTE BAUD 1200 sets the baud of the data port to 1200.
REMOTE BAUD 9600 sets the baud of the data port to 9600.
Input Example:
REMOTE BAUD
Output Response:
REMOTE BAUD 9600
Only the command REMOTE BAUD gives a response.
R
EPORT
Purpose:
Reports all alarm point descriptions.
Format:
REPORT ALL
REPORT ID #
REPORT ID # DISP #
REPORT ID # DISP # POINT #
Remarks:
Reports all alarm point descriptions by ID number, ID and
display number, or by ID and display and point number.
PRINTER SYNTAX