![Dantel 46062-02 Installation & Operation Manual Download Page 32](http://html1.mh-extra.com/html/dantel/46062-02/46062-02_installation-and-operation-manual_3459426032.webp)
P
AGE
32
46062-0299 <90-00016>
NOTE:
If you do not enter anything for 60 seconds, the path will
automatically disconnect and the system will return to polling
alarms.
When the CALL command is active, you can only use the MAP’s
Printer Syntax commands. You cannot use the Status Monitor
Syntax. To determine if the CALL command is still active, type
the letter Q. If you get a response to the Q (Query) command,
you are still in the MAP’s Printer Syntax. If you get a COM-
MAND ERROR response, the CALL command has timed out
and you are in the Status Monitor Syntax.
Input Example:
CALL 1
Output Response:
Everything that is displayed on the screen is the MAP’s return
response.
NOTE:
If the message “This is a slave” appears, it means one of the
following:
♦
This Status Monitor is a slave; that is, it is in a listening
mode only.
♦
The Status Monitor does not have a database configuration
to tell it how to operate. Configure the Status Monitor.
♦
The Status Monitor is a master, but it is not communicating
with 46020 Multiple Alarm Processors (MAPs). Investigate
the communications failure.
C
ONFIGURE
Purpose:
Displays, defines, reserves or clears the system configuration.
Format:
CONFIGURE
CONFIGURE POSITION
CONFIGURE POSITION #
CONFIGURE ID #-# DISPLAY #-#
CONFIGURE POSITION # SKIP #
CONFIGURE CLEAR ALL
CONFIGURE CLEAR #
PRINTER SYNTAX