Bit 11, Relay 01:
Bit 11 = "0": Relay not activated. Bit 11 = "1": Relay 01 activated provided that
Control word bit
11
is chosen in par. 5-40
Function relay
.
Bit 12, Relay 04:
Bit 12 = "0": Relay 04 is not activated. Bit 12 = "1": Relay 04 is activated provided that
Control
word bit 12
is chosen in par. 5-40
Function relay
.
Bit 13/14, Selection of set-up:
Use bits 13 and 14 to choose from the four
menu set-ups according to the shown table: .
Set-up
Bit 14
Bit 13
1
0
0
2
0
1
3
1
0
4
1
1
The function is only possible when
Multi Set-
Ups
is selected in par. 0-10
Active Set-Up
NB!
Make a selection in par. 8-55
Set-up select
to define how Bit
13/14 gates with the corre-
sponding function on the digital
inputs.
Bit 15 Reverse:
Bit 15 = ’0’: No reversing. Bit 15 = ’1’: Reversing. In the default setting, reversing is set to digital
in par. 8-54
Reversing Select
. Bit 15 causes reversing only when Ser. communication, Logic or or
Logic and is selected.