Illustration 5.10: Motor connection for enclosure
B1 and B2
Illustration 5.11: Motor connection for enclosure
C1 and C2
All types of three-phase asynchronous stand-
ard motors can be connected to the frequency
converter. Normally, small motors are star-
connected (230/400 V, D/Y). Large motors are
delta-connected (400/600 V, D/Y). Refer to
the motor name plate for correct connection
mode and voltage.
NB!
In motors without phase insulation paper or other insulation reinforcement suitable
for operation with voltage supply (such as a frequency converter), fit an LC filter on
the output of the frequency converter.
No.
96
97
98
Motor voltage 0-100%
U
V
W
of mains voltage.
3 wires out of motor
U1
V1
W1
6 wires out of motor, Delta-connected
W2
U2
V2
U1
V1
W1
6 wires out of motor, Star-connected
U2, V2, W2 to be interconnected separately
(optional terminal block)
No.
99
Earth connection
PE
VLT
®
HVAC Drive Design Guide
5. How to Install
MG.11.B2.02 - VLT
®
is a registered Danfoss trademark
89
5