[2]
Drive ready
The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3]
Drive ready /
remote control
The frequency converter is ready for
operation and is in Auto On mode.
[4]
Stand-by / no
warning
The frequency converter is ready for
operation. No start or stop command is
been given (start/disable). There are no
warnings.
[5]
Running
The motor is running.
[6]
Running / no
warning
The output speed is higher than the
speed set in
1-81 Min Speed for Function at
. The motor is running and
there are no warnings.
[8]
Run on
reference / no
warning
The motor runs at reference speed.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or
warning
An alarm or a warning activates the
output.
[11]
At torque limit The torque limit set in
or
has been exceeded.
[12]
Out of current
range
The motor current is outside the range set
in
[13]
Below current,
low
The motor current is lower than set in
[14]
Above current,
high
The motor current is higher than set in
.
[15]
Out of speed
range
The output speed is outside the range set
in
and
.
[16]
Below speed,
low
The output speed is lower than the
setting in
[17]
Above speed,
high
The output speed is higher than the
setting in
[18]
Out of
feedback
range
The feedback is outside the range set in
and
.
[19]
Below
feedback low
The feedback is below the limit set in
.
[20]
Above
feedback high
The feedback is above the limit set in
.
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
[25]
Reverse
Reversing. Logic ‘1’ =
relay activated, 24 V
DC when CW rotation of the motor. Logic
‘0’ = relay not activated, no signal, when
CCW rotation of the motor.
[26]
Bus OK
Active communication (no time-out) via
the serial communication port.
[27]
Torque limit
and stop
Use in performing a coasting stop and in
torque limit condition. If the frequency
converter has received a stop signal and is
at the torque limit, the signal is Logic ‘0’.
[28]
Brake, no
warning
The brake is active and there are no
warnings.
[29]
Brake ready,
no fault
The brake is ready for operation and there
are no faults.
[30]
Brake fault
(IGBT)
The output is Logic ‘1’ when the brake
IGBT is short-circuited. Use this function to
protect the frequency converter if there is
a fault on the brake modules. Use the
output/relay to cut out the main voltage
from the frequency converter.
[35]
External
Interlock
External Interlock function has been
activated via one of the digital inputs.
[40]
Out of ref
range
[41]
Below
reference low
[42]
Above
reference high
[45]
Bus Ctrl
[46]
Bus Ctrl 1 if
timeout
[47]
Bus Ctrl 0 if
timeout
[55]
Pulse output
[60]
Comtor 0
See parameter group 13-1*. If Comtor 0 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[61]
Comtor 1
See parameter group 13-1*. If Comtor 2 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[62]
Comtor 2
See parameter group 13-1*. If Comtor 2 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[63]
Comtor 3
See parameter group 13-1*. If Comtor 3 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[64]
Comtor 4
See parameter group 13-1*. If Comtor 4 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[65]
Comtor 5
See parameter group 13-1*. If Comtor 5 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[70]
Logic Rule 0
See parameter group 13-4*. If Logic Rule 0
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[71]
Logic Rule 1
See parameter group 13-4*. If Logic Rule 1
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[72]
Logic Rule 2
See parameter group 13-4*. If Logic Rule 2
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[73]
Logic Rule 3
See parameter group 13-4*. If Logic Rule 3
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
Parameter Description