Par. LC-43
Logic Rule Operator 2
Par. LC-41
Logic Rule Operator 1
Par. LC-40
Logic Rule Boolean 1
Par. LC-42
Logic Rule Boolean 2
Par. LC-44
Logic Rule Boolean 3
130BB673.10
Illustration 3.32
Priority of calculation
The results of
,
and
are calculated
first. The outcome (TRUE/FALSE) of this calculation is
combined with the settings of
and
, yielding the final result
(TRUE/FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[0]
*
False
Enters the fixed value of FALSE in the
logic rule.
[1]
True
Enters the fixed value TRUE in the
logic rule.
[2]
Running
See parameter group 5-3* for further
description.
[3]
In range
See parameter group 5-3* for further
description.
[4]
On reference
See parameter group 5-3* for further
description.
[5]
Torque limit
See parameter group 5-3* for further
description.
[6]
Current Limit
See parameter group 5-3* for further
description.
[7]
Out of current
range
See parameter group 5-3* for further
description.
[8]
Below I low
See parameter group 5-3* for further
description.
[9]
Above I high
See parameter group 5-3* for further
description.
[10] Out of speed
range
[11] Below speed low
See parameter group 5-3* for further
description.
[12] Above speed high
See parameter group 5-3* for further
description.
[13] Out of feedb.
range
See parameter group 5-3* for further
description.
[14] Below feedb. low
See parameter group 5-3* for further
description.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[15] Above feedb. high See parameter group 5-3* for further
description.
[16] Thermal warning
See parameter group 5-3* for further
description.
[17] Mains out of range See parameter group 5-3* for further
description.
[18] Reversing
See parameter group 5-3* for further
description.
[19] Warning
See parameter group 5-3* for further
description.
[20] Alarm (trip)
See parameter group 5-3* for further
description.
[21] Alarm (trip lock)
See parameter group 5-3* for further
description.
[22] Comparator 0
Use the result of comtor 0 in the logic
rule.
[23] Comparator 1
Use the result of comtor 1 in the logic
rule.
[24] Comparator 2
Use the result of comtor 2 in the logic
rule.
[25] Comparator 3
Use the result of comtor 3 in the logic
rule.
[26] Logic rule 0
Use the result of logic rule 0 in the
logic rule.
[27] Logic rule 1
Use the result of logic rule 1 in the
logic rule.
[28] Logic rule 2
Use the result of logic rule 2 in the
logic rule.
[29] Logic rule 3
Use the result of logic rule 3 in the
logic rule.
[30] SL Time-out 0
Use the result of timer 0 in the logic
rule.
[31] SL Time-out 1
Use the result of timer 1 in the logic
rule.
[32] SL Time-out 2
Use the result of timer 2 in the logic
rule.
[33] Digital input DI18
Use the value of DI18 in the logic rule
(High = TRUE).
[34] Digital input DI19
Use the value of DI19 in the logic rule
(High = TRUE).
[35] Digital input DI27
Use the value of DI27 in the logic rule
(High = TRUE).
[36] Digital input DI29
Use the value of DI29 in the logic rule
(High = TRUE).
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
88
MG16H102 - VLT
®
is a registered Danfoss trademark
3
3