0-20 Display Line 1.1 Small
Option:
Function:
[1007] Readout Bus Off
Counter
View the number of Bus Off events
since the last power-up.
[1013] Warning Parameter
View a DeviceNet-specific warning
word. One sete bit is assigned to
every warning.
[1501] Running Hours
View the number of running hours
of the motor.
[1502] kWh Counter
View the mains power consumption
in kWh.
[1600] Control Word
View the Control Word sent from
the frequency converter via the
serial communication port in hex
code.
[1601] Reference [Unit]
Total reference (sum of digital/
analog/preset/bus/freeze ref./catch
up and slow-down) in selected unit.
[1602] Reference [%]
Total reference (sum of digital/
analog/preset/bus/freeze ref./catch
up and slow-down) in percent.
[1603] Status Word
Present status word
[1605] Main Actual Value
[%]
View the two-byte word sent with
the Status word to the bus Master
reporting the Main Actual Value.
[1609] Custom Readout
View the user-defined readouts as
defined in
,
and
[1610] Power [kW]
Actual power consumed by the
motor in kW.
[1611] Power [hp]
Actual power consumed by the
motor in HP.
[1612] Motor Voltage
Voltage supplied to the motor.
[1613] Frequency
Motor frequency, i.e. the output
frequency from the frequency
converter in Hz.
[1614] Motor current
Phase current of the motor
measured as effective value.
[1615] Frequency [%]
Motor frequency, i.e. the output
frequency from the frequency
converter in percent.
[1616] Torque [Nm]
Present motor load as a percentage
of the rated motor torque.
[1617] Speed [RPM]
Motor speed reference. Actual
speed will depend on slip compen-
sation being used (compensation
set in
). If not
used, actual speed will be the value
0-20 Display Line 1.1 Small
Option:
Function:
read in the display minus motor
slip.
[1618] Motor Thermal
Thermal load on the motor,
calculated by the ETR function. See
also parameter group 1-9* Motor
Temperature.
[1622] Torque [%]
Shows the actual torque produced,
in percentage.
[1630] DC Link Voltage
Intermediate circuit voltage in the
frequency converter.
[1632] Brake Energy /s
Present brake power transferred to
an external brake resistor.
Stated as an instantaneous value.
[1633] Brake Energy /2 min Brake power transferred to an
external brake resistor. The mean
power is calculated continuously for
the most recent 120 seconds.
[1634] Heatsink Temp.
Present heat sink temperature of
the frequency converter. The cut-
out limit is 95 ± 5
°
C; cutting back
in occurs at 70 ± 5
°
C.
[1635] Inverter Thermal
Percentage load of the inverters
[1636] Inv. Nom. Current
Nominal current of the frequency
converter
[1637] Inv. Max. Current
Maximum current of the frequency
converter
[1638] SL Controller State
State of the event executed by the
control
[1639] Control Card Temp.
Temperature of the control card.
[1650] External Reference
Sum of the external reference as a
percentage, i.e. the sum of analog/
pulse/bus.
[1652] Feedback[Unit]
Reference value from programmed
digital input(s).
[1653] Digi Pot Reference
View the contribution of the digital
potentiometer to the actual
reference Feedback.
[1654] Feedback 1 [Unit]
View the value of Feedback 1. See
also 20-0*.
[1655] Feedback 2 [Unit]
View the value of Feedback 2. See
also 20-0*.
[1656] Feedback 3 [Unit]
View the value of Feedback 3. See
also parameter group 20-0*.
[1660] Digital Input
Displays the status of the digital
inputs. Signal low = 0; Signal high
= 1.
Regarding order, see
. Bit 0 is at the extreme right.