2-16 AC brake Max. Current
Range:
Function:
100 %
*
[ 0 - 1000.0
%]
Enter the maximum permissible current
when using AC brake to avoid
overheating of motor windings. The AC
brake function is available in Flux mode
only.
NOTE
will not have effect when
= [1] PM, non salient SPM.
2-17 Over-voltage Control
Option:
Function:
[0]
Disabled
No OVC required.
[2]
*
Enabled
Activates OVC.
NOTE
will not have effect when
= [1] PM, non salient SPM.
NOTE
The ramp time is automatically adjusted to avoid tripping
of the frequency converter.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark