40% duty cycle, vertical braking, T2
FC 202
Vertical braking 40% duty cycle
Frequency converter data
Brake resistor data
Installation
R
rec
[
Ω
]
P
br,cont.
[kW]
Danfoss part number
Cable
cross-
section
[mm
2
]
Thermo
relay
[A]
Mains
type
P
m
[kW]
R
min
[
Ω
]
R
br,nom
[
Ω
]
Wire IP54
Screw
terminal
IP21
Screw
terminal
IP65
Bolt
connection
IP20
T2
0.25
380
691.3
630
0.100
175u3002
-
-
-
1.5
0.4
T2
0.37
380
466.7
410
0.100
175u3004
-
-
-
1.5
0.5
T2
0.55
275
313.7
300
0.200
175u3096
-
-
-
1.5
0.8
T2
0.75
188
230.0
200
0.200
175u3008
-
-
-
1.5
0.9
T2
1.1
130
152.9
145
0.300
175u3300
-
-
-
1.5
1.3
T2
1.5
81.0
110.5
100
0.450
175u3301
175u3402
175u3401
-
1.5
2
T2
2.2
58.5
74.1
70
0.570
175u3302
175u3404
175u3403
-
1.5
2.7
T2
3
45.0
53.7
48
0.960
175u3303
175u3406
175u3405
-
1.5
4.2
T2
3.7
31.5
39.9
35
1.130
175u3304
175u3408
175u3407
-
1.5
5.4
T2
5.5
22.5
28.7
27
1.400
175u3305
175u3410
175u3409
-
1.5
6.8
T2
7.5
17.7
20.8
18
2.200
175u3306
175u3412
175u3411
-
1.5
10.4
T2
11
12.6
14.0
13
3.200
175u3307
175u3414
175u3413
-
2.5
14.7
T2
15
8.7
10.2
9.0
5.500
-
175u3176
175u3177
-
4
23
T2
18.5
5.3
8.2
5.7
6.000
-
-
-
175u3233
10
33
T2
22
5.1
6.9
5.7
8.000
-
-
-
175u3234
10
38
T2
30
3.2
5.0
3.5
9.000
-
-
-
175u3235
16
51
T2
37
3.0
4.1
3.5
14.000
-
-
-
175u3224
25
63
T2
45
2.4
3.3
2.8
17.000
-
-
-
175u3227
35
78
Table 8.12 T2, Vertical Braking 40% Duty Cycle
Selection Guide
Design Guide
42
Danfoss A/S © Rev. 05/2014 All rights reserved.
MG90O202