P/N
Resi-
stance
Continuous
power 100%
load
Pulse
load
power
10%
duty
cycle
1)
Pulse
load
power
40%
duty
cycle
1)
Temp.
switch
2)
3)
Terminal max wire
cross-section
Wire cross-section
4)
Temp. switch
Power cables
Temp. switch
Power cables
[
Ω
]
[W]
[kW]
[kW]
Type
[mm
2
] [AWG]
[mm
2
]
[AWG] [mm
2
] [AWG] [mm
2
] [AWG]
175U3479
22
3200
39.9
9.9
1
4.0
12
16
6
-
-
-
-
175U3480
22
3200
39.9
9.9
1
4.0
12
16
6
-
-
-
-
175U3481
105
790
9.5
2.37
1
4.0
12
16
6
-
-
-
-
175U3482
105
790
9.5
2.37
1
4.0
12
16
6
-
-
-
-
175U3483
5.7
1700
21.1
5.27
1
4.0
12
16
6
-
-
-
-
175U3484
5.7
1700
21.1
5.27
1
4.0
12
16
6
-
-
-
-
Table 9.1 Electrical Data: Product Types 9xx
1) Based on reference profiles with 30 s repetition rates
2) Temperature switch type 1: 2 A. 250 V AC. Normally closed (NC). Enables at 180
°
C
3) Temperature switch type 2: 10 A. 250 V AC. Normally closed (NC). Enables at 260
°
C
4) Only for versions with fixed cables. All cables are 1000 mm unscreened cables.
Specifications
Design Guide
MG90O202
Danfoss A/S © Rev. 05/2014 All rights reserved.
73
9