7.4.1 Fault Messages - Active Filter
WARNING 1, 10 volts low
The control card voltage is below 10 V from terminal 50.
Remove some of the load from terminal 50, as the 10 V
supply is overloaded. Max. 15 mA or minimum 590
Ω
.
Fault messages - active filter
WARNING/ALARM 2, Live zero error
The signal on terminal 53 or 54 is less than 50% of the
value set in parameters 6-10, 6-12, 6-20 or 6-22.
WARNING 4, Mains phase loss
A phase is missing on the supply side, or the line voltage
imbalance is too high.
WARNING 5, DC link voltage high
The intermediate circuit voltage (DC) is higher than the
high voltage warning limit. The unit is still active.
WARNING 6, DC link voltage low
The intermediate circuit voltage (DC) is below the
undervoltage limit of the control system. The unit is still
active.
WARNING/ALARM 7, DC overvoltage
If the intermediate circuit voltage exceeds the limit, the
unit trips.
WARNING/ALARM 8, DC undervoltage
If the intermediate circuit voltage (DC) drops below the
under voltage limit, the filter checks if a 24 V backup
supply is connected. If not, the unit trips. Make sure the
AC line voltage matches the nameplate specification.
WARNING/ALARM 13, Overcurrent
the unit current limit has been exceeded.
ALARM 14, Ground fault
The sum current of the IGBT CTs does not equal zero.
Check if the resistance of any phase to ground has a low
value. Check both before and after line power contactor.
Ensure IGBT current transducers, connection cables, and
connectors are ok.
ALARM 15, Incomp. Hardware
A mounted option is incompatible with the present control
card SW/HW.
ALARM 16, Short-circuit
There is a short-circuit in the output. Turn off the unit and
correct the error.
WARNING/ALARM 17, Control word timeout
There is no communication to the unit.
The warning is only active when
parameter 8-04 Control
Timeout Function
is not set to off.
Possible correction: Increase
parameter 8-03 Control Timeout
Time
. Change
parameter 8-04 Control Timeout Function
WARNING 23, Internal fan fault
Internal fans have failed due to defect hardware or fans
not mounted.
WARNING 24, External fan fault
External fans have failed due to defect hardware or fans
not mounted.
ALARM 29, Heatsink temp
The maximum temperature of the heatsink has been
exceeded. The temperature fault is not reset until the
temperature falls below a defined heatsink temperature.
ALARM 33, Inrush fault
Check whether a 24 V external DC supply has been
connected.
WARNING/ALARM 34, Fieldbus communication fault
The serial communication bus on the communication
option card is not working.
WARNING/ALARM 35, Option Fault:
Contact Danfoss or supplier.
ALARM 38, Internal fault
Contact Danfoss or supplier.
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
WARNING 40, Overload of Digital Output Terminal 27
Check the load connected to terminal 27 or remove short-
circuit connection.
WARNING 41, Overload of Digital Output Terminal 29
Check the load connected to terminal 29 or remove short-
circuit connection.
WARNING 43, Ext. Supply (option)
The external 24 V DC supply voltage on the option is not
valid.
ALARM 46, Power card supply
The supply on the power card is out of range.
WARNING 47, 24 V supply low
Contact Danfoss or supplier.
WARNING 48, 1.8 V supply low
Contact Danfoss or supplier.
WARNING/ALARM/TRIP 65, Control card overtemperature
Control card overtemperature: The cutout temperature of
the control card is 176°F [80
°
C].
WARNING 66, Heatsink temperature low
This warning is based on the temperature sensor in the
IGBT module.
Troubleshooting:
The heatsink temperature measured as 32°F [0
°
C] could
indicate that the temperature sensor is defective, causing
the fan speed to increase to the maximum. If the sensor
wire between the IGBT and the gate drive card is discon-
Status Messages
Installation Manual
MG37A322
Danfoss A/S © Rev. 04/2015 All rights reserved.
81
7
7