Surroundings
Enclosure
IP21, IP54
Vibration test
1.0 g
Relative humidity
5%–95% IEC 721-3-3; class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class kD
Test method according to IEC 60068-2-43 H
2
S (10 days)
Ambient temperature
- with derating
max. NA °F [
°
C]
- with full output current (short temperature overload)
max. 113°F [45
°
C]
- at full continuous output current (24 hours)
max. 104°F [40
°
C]
Minimum ambient temperature during full-scale operation
32°F [0
°
C]
Minimum ambient temperature at reduced performance
14°F [-10
°
C]
Temperature during storage/transport
+13° to 158°F [-25° to +70
°
C]
Maximum altitude above sea level without derating
3300 ft [1000 m]
Maximum altitude above sea level with derating
10,000 ft [3000 m]
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Control card performance
Scan interval
5 ms
Control card, USB serial communication
USB standard
1.1 (full speed)
USB plug
USB type B “device” plug
Generic specifications
Maximum parallel filters
4 on same CT set
Filter efficiency
97%
Typical average switching frequency
3.0–4.5 kHz
Response time (reactive and harmonic)
< 0.5 ms
Settling time - reactive current control
< 20 ms
Settling time - harmonic current control
< 20 ms
Overshoot – reactive current control
<10%
Overshoot – Harmonic current control
<10%
Connection to PC is carried out via a standard host/device USB cable. The USB connection is galvanically isolated from the
supply voltage (PELV) and other high-voltage terminals. The USB connection is not galvanically isolated from ground
protection. Use only isolated laptop/PC as connection to the USB connector on the unit or an isolated USB cable/drive.
Protection and features
•
Temperature monitoring of the heatsink ensures that the active filter trips if the temperature reaches a predefined
level. An overload temperature cannot be reset until the temperature of the heatsink is below the acceptable
values.
•
If a line phase is missing, the active filter trips.
•
The active filter has a short circuit protection current rate of 100 kA if properly fused
•
Monitoring of the intermediate circuit voltage ensures that the filter trips if the intermediate circuit voltage is too
low or too high.
•
The active filter monitors the line power current as well as internal currents to ensure that current levels do not
reach critical levels. If current exceeds a critical level, the filter trips.
Specifications
Installation Manual
MG37A322
Danfoss A/S © Rev. 04/2015 All rights reserved.
101