4.10 Final Set-up and Test
Before operating the frequency converter, perform a final
test of the installation:
1.
Locate the motor name plate to find out whether
the motor is star- (Y) or delta- connected (
Δ)
.
2.
Enter the motor name plate data in the
parameter list. Access the list by pressing the
[Quick Menu] key and selecting
Q2 Quick Set-up
.
See
1.
Parameter 1-20 Motor Power [kW]
Parameter 1-21 Motor Power [HP]
2.
Parameter 1-22 Motor Voltage
3.
Parameter 1-23 Motor Frequency
4.
Parameter 1-24 Motor Current
5.
Parameter 1-25 Motor Nominal Speed
Table 4.11 Quick Set-up Parameters
3~ MOTOR NR. 1827421 2003
S/E005A9
1,5
KW
n2 31,5
/MIN.
400
Y
V
n1 1400
/MIN.
50
Hz
cos 0,80
3,6
A
1,7L
B
IP 65
H1/1A
130B
T307.10
BAUER D-7 3734 ESLINGEN
Figure 4.19 Motor Name Plate
3.
Perform an automatic motor adaptation (AMA) to
ensure optimum performance.
3a
Connect terminal 27 to terminal 12 or
set
parameter 5-12 Terminal 27 Digital
Input
to
[0] No operation
.
3b
Activate the AMA in
parameter 1-29 Automatic Motor
Adaptation (AMA)
.
3c
Select either complete or reduced AMA.
If an LC filter is mounted, run only the
reduced AMA, or remove the LC filter
during the AMA procedure.
3d
Press [OK]. The display shows
Press
[Hand On] to start
.
3e
Press [Hand On]. A progress bar
indicates whether the AMA is in
progress.
Electrical Installation
Installation Manual
MG37A322