Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1
R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
130BB841.10
Function
Setting
parameter 1-00
Configuration
Mode
[0] Speed
open-loop
parameter 1-01
Motor Control
Principle
[1] VVC
+
parameter 5-40
Function Relay
[32] Mech.
brake ctrl.
Parameter 5-10 T
erminal 18
Digital Input
[8] Start*
parameter 5-11
Terminal 19
Digital Input
[11] Start
reversing
parameter 1-71
Start Delay
0.2
parameter 1-72
Start Function
[5] VVC
+
/
FLUX
Clockwise
parameter 1-76
Start Current
I
m,n
parameter 2-20
Release Brake
Current
App.
dependent
parameter 2-21
Activate Brake
Speed [RPM]
Half of
nominal slip
of the motor
*=Default Value
Notes/comments:
Table 6.14 Mechanical Brake Control (Open-loop)
Start (18)
Start
reversing (19)
Relay output
Speed
Time
Current
1-71
1-71
2-21
2-21
1-76
Open
Closed
130BB842.10
Figure 6.4 Mechanical Brake Control (Open-loop)
Application Examples
Installation Manual
MG37A322
Danfoss A/S © Rev. 04/2015 All rights reserved.
67
6
6