4.1.11 Initialisation to Default Settings
There are two ways to initialise the frequency converter to default: Recommended initialisation and manual initialisation.
Please be aware that they have different impact according to the below description.
Recommended initialisation (via par. 14-22
Operation Mode
)
1.
Select par. 14-22
Operation Mode
2.
Press [OK]
3.
Select “Initialisation” (for NLCP select “2”)
4.
Press [OK]
5.
Remove power to unit and wait for display to turn off.
6.
Reconnect power and the frequency converter is reset. Note
that first start-up takes a few more seconds.
7.
Press [Reset]
par. 14-22
Operation Mode
initialises all except:
par. 14-50
RFI Filter
par. 8-30
Protocol
par. 8-31
Address
par. 8-32
Baud Rate
par. 8-35
Minimum Response Delay
par. 8-36
Max Response Delay
par. 8-37
Maximum Inter-Char Delay
par. 15-00
Operating Hours
to par. 15-05
Over Volt's
par. 15-20
Historic Log: Event
to par. 15-22
Historic Log: Time
par. 15-30
Alarm Log: Error Code
to par. 15-32
Alarm Log: Time
NB!
Parameters selected in par. 0-25
My Personal Menu
, will stay present, with default factory setting.
Manual initialisation
NB!
When carrying out manual initialisation, serial communication, RFI filter settings and fault log settings are reset.
Removes parameters selected in par. 0-25
My Personal Menu
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while
power up for Graphical LCP (GLCP).
2b. Press [Menu] while power up for LCP 101, Numerical Display
3. Release the keys after 5 s.
4. The frequency converter is now programmed according to
default settings.
This parameter initialises all except:
par. 15-00
Operating Hours
par. 15-03
Power Up's
par. 15-04
Over Temp's
par. 15-05
Over Volt's
4.1.12 RS-485 Bus Connection
One or more frequency converters can be connected to a controller (or
master) using the RS-485 standard interface. Terminal 68 is connected
to the P signal (TX+, RX+), while terminal 69 is connected to the N signal
(TX-,RX-).
If more than one frequency converter is connected to a master, use par-
allel connections.
Illustration 4.10: Connection example.
In order to avoid potential equalizing currents in the screen, earth the cable screen via terminal 61, which is connected to the frame via an RC-link.
Bus termination
The RS-485 bus must be terminated by a resistor network at both ends. If the drive is the first or the last device in the RS-485 loop, set the switch S801
on the control card for ON.
4 How to operate the frequency converter
VLT AQUA High Power Operation Instructions
90