3.2.4 Lifting
Always lift the frequency converter in the dedicated lifting eyes. For all D and E2 (IP00) frames, use a bar to avoid bending the lifting holes of the frequency
converter.
Illustration 3.3: Recommended lifting method, frame sizes D and E .
NB!
The lifting bar must be able to handle the weight of the frequency converter. See
Mechanical Dimensions
for the weight of the different
frame sizes. Maximum diameter for bar is 25 cm (1 inch). The angle from the top of the drive to the lifting cable should be 60 degrees
or greater.
Illustration 3.4: Recommended lifting method, frame size
F1.
Illustration 3.5: Recommended lifting method, frame size
F2.
VLT AQUA High Power Operation Instructions
3 How to Install
MG.20.P3.02 - VLT
®
is a registered Danfoss trademark
15