NB!
A doorfan(s) is required on the Rittal cabinet to remove the loses not contained in the backchannel of the drive. The minimum doorfan(s)
airflow required at the drive maximum ambient for the D3 and D4 is 391 m^3/h (230 cfm). The minimum doorfan(s) airflow required
at the drive maximum ambient for the E2 is 782 m^3/h (460 cfm). If the ambient is below maximum or if additional components, heat
loses, are added within the enclosure a calculation must be made to ensure the proper airflow is provided to cool the inside of the
Rittal enclosure.
Ordering Information
Rittal TS-8 Enclosure
Frame D3 Kit Part No.
Frame D4Kit Part No.
Frame E2 Part No.
1800 mm
176F1824
176F1823
Not possible
2000 mm
176F1826
176F1825
176F1850
2200 mm
176F0299
Kit Contents
•
Ductwork components
•
Mounting hardware
•
Gasket material
•
Delivered with D3 and D4 frame kits:
•
175R5639 - Mounting templates and top/bottom cut out for Rittal enclosure.
•
Delivered with E2 frame kits:
•
175R1036 - Mounting templates and top/bottom cut out for Rittal enclosure.
All fasteners are either:
•
10 mm, M5 Nuts torque to 2.3 Nm (20 in-lbs)
•
T25 Torx screws torque to 2.3 Nm (20 in-lbs)
NB!
Please see the
Duct Kit Instruction Manual, 175R5640,
for further information
3 How to Install
VLT AQUA High Power Operation Instructions
40
MG.20.P3.02 - VLT
®