NB!
It is important to set motor par. 1-2* Motor Data correctly, since these form part of the AMA algorithm. An AMA must be performed
to achieve optimum dynamic motor performance. It may take up to 10 min., depending on motor power rating.
NB!
Avoid generating external torque during AMA
NB!
If one of the settings in par. 1-2* Motor Data is changed, par. 1-30
Stator Resistance (Rs)
to par. 1-39
Motor Poles
, the advanced
motor parameters, will return to default setting.
This parameter cannot be adjusted while the motor is running
NB!
Full AMA should be run without filter only while reduced AMA should be run with filter.
See section
Automatic Motor Adaptation
- application example.
5.2.4 3-0* Reference Limits
Parameters for setting the reference unit, limits and ranges.
3-02 Minimum Reference
Range:
Function:
0.000 Ref-
erenceFeed-
backUnit*
[-999999.999 - par. 3-03 Referen-
ceFeedbackUnit]
Enter the desired minimum value for the remote reference. The Minimum Reference value and unit
matches the configuration choice made in par. 1-00
and par. 20-12
Reference/
Feedback Unit
, respectively.
NB!
If operating with par. 1-00, Configuration Mode set for Closed Loop [3], par.
20-13, Minimum Reference/Feedb. must be used.
3-03 Maximum Reference
Range:
Function:
50.000 Ref-
erenceFeed-
backUnit*
[par. 3-02 - 999999.999 Referen-
ceFeedbackUnit]
Enter the maximum acceptable value for the remote reference. The Maximum Reference value and
unit matches the configuration choice made in par. 1-00
and par. 20-12
Ref-
erence/Feedback Unit
, respectively.
NB!
If operating with par. 1-00, Configuration Mode set for Closed Loop [3], par.
20-14, Maximum Reference/Feedb. must be used.
VLT AQUA High Power Operation Instructions
5 How to programme the frequency converter