EXAMPLE 3:
Variable value= REFERENCE, range= Min ref - Max ref
Range needed for output= Min ref (0%) - Max ref (100%), 0-10 mA
Output signal 0 or 4 mA is needed at Min ref - set par. 6-51
to 0%
Output signal 10 mA is needed at Max ref (100% of range) - set par. 6-52
to 200%
(20 mA / 10 mA x 100%=200%).
5.2.9 Drive Closed Loop, 20-**
This parameter group is used for configuring the closed loop PID Controller, that controls the output frequency of the frequency converter.
20-12 Reference/Feedback Unit
Option:
Function:
[0]
None
[1] *
%
[5]
PPM
[10]
1/min
[11]
RPM
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m
3
/s
[24]
m
3
/min
[25]
m
3
/h
5 How to programme the frequency converter