[105]
Torque 0-Tnom
: 0 - Motor rated torque, (0-20 mA)
[106]
Power 0-Pnom
: 0 - Motor rated power, (0-20 mA)
[107]
Speed 0-HighLim
: 0 - Speed High Limit (par. 4-13 and par. 4-14), (0-20 mA)
[113]
Ext. Closed Loop 1
: 0 - 100%, (0-20 mA)
[114]
Ext. Closed Loop 2
: 0 - 100%, (0-20 mA)
[115]
Ext. Closed Loop 3
: 0 - 100%, (0-20 mA)
[130]
Out frq 0-100 4-20mA
: 0 - 100 Hz
[131]
Reference 4-20mA
: Minimum Reference - Maximum Reference
[132]
Feedback 4-20mA
: -200% to +200% of par. 20-14
[133]
Motor cur. 4-20mA
: 0 - Inverter Max. Current (par. 16-37
Inv. Max. Current
)
[134]
Torq.0-lim 4-20 mA
: 0 - Torque limit (par. 4-16)
[135]
Torq.0-nom 4-20mA
: 0 - Motor rated torque
[136]
Power 4-20mA
: 0 - Motor rated power
[137]
Speed 4-20mA
: 0 - Speed High Limit (par. 4-13 and par. 4-14)
[139]
Bus ctrl.
: 0 - 100%, (0-20 mA)
[140]
Bus ctrl. 4-20 mA
: 0 - 100%
[141]
Bus ctrl t.o.
: 0 - 100%, (0-20 mA)
[142]
Bus ctrl t.o. 4-20mA
: 0 - 100%
[143]
Ext. CL 1 4-20mA
: 0 - 100%
[144]
Ext. CL 2 4-20mA
: 0 - 100%
[145]
Ext. CL 3 4-20mA
: 0 - 100%
NB!
Values for setting the Minimum Reference is found in open loop par. 3-02
and for closed loop par. 20-13
Minimum Reference/
Feedb.
- values for maximum reference for open loop is found in par. 3-03
and for closed loop par. 20-14
Maximum Reference/
Feedb.
.
6-51 Terminal 42 Output Min Scale
Range:
Function:
0.00 %*
[0.00 - 200.00 %]
Scale for the minimum output (0 or 4 mA) of the analogue signal at terminal 42.
Set the value to be the
percentage
of the full range of the variable selected in par. 6-50
.
5 How to programme the frequency converter
VLT AQUA High Power Operation Instructions