6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
100.000 N/
A*
[-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the high voltage/high current value set in
par. 6-21
and par. 6-23 Terminal
54 High Current
.
6-50 Terminal 42 Output
Option:
Function:
Select the function of Terminal 42 as an analog current output.
[0] *
No operation
[100]
Output freq. 0-100
: 0 - 100 Hz
[101]
Reference Min-Max
: Minimum reference - Maximum reference
[102]
Fe-200%
: -200% to +200% of par. 2-14
[103]
Motor cur. 0-Imax
: 0 - Inverter Max. Current (par. 16-37)
[104]
Torque 0-Tlim
: 0 - Torque limit (par. 4-16)
[105]
Torque 0-Tnom
: 0 - Motor rated torque
[106]
Power 0-Pnom
: 0 - Motor rated power
[107]
Speed 0-HighLim
: 0 - Speed High Limit (par. 4-13 and par. 4-14)
[113]
Ext. Closed Loop 1
0 - 100%
[114]
Ext. Closed Loop 2
0 - 100%
[115]
Ext. Closed Loop 3
0 - 100%
[130]
Out frq 0-100 4-20mA
:0 - 100 Hz
[131]
Reference 4-20mA
Minimum Reference - Maximum Reference
[132]
Feedback 4-20mA
-200% to +200% of par. 2-14
[133]
Motor cur. 4-20mA
0 - Inverter Max. Current (par. 16-37 Inv.
Max. Current
)
[134]
Torq.0-lim 4-20 mA
:0 - Torque limit (par. 4-16)
[135]
Torq.0-nom 4-20mA
:0 - Motor rated torque
[136]
Power 4-20mA
0 - Motor rated power
[137]
Speed 4-20mA
0 - Speed High Limit (par. 4-13 and par. 4-14)
[139]
Bus ctrl.
0 - 100%
[140]
Bus ctrl. 4-20 mA
0 - 100%
[141]
Bus ctrl t.o.
0 - 100%
[142]
Bus ctrl t.o. 4-20mA
0 - 100%
[143]
Ext. CL 1 4-20mA
0 - 100%
[144]
Ext. CL 2 4-20mA
0 - 100%
[145]
Ext. CL 3 4-20mA
0 - 100%
NB!
Values for setting the Minimum Reference is found in par. 3-02
and par. 20-13 Minimum
Reference/Feedb.
- values for Maximum
Reference is found in par. 3-03
and par. 20-14 Maximum
Reference/Feedb.
.
8. How to programme the frequency converter
VLT
®
AQUA Drive
Operating Instructions