[1013]
Warning Parameter
View a DeviceNet-specific warning word. One separate bit is assigned to every warning.
[1115]
LON Warning Word
Shows the LON-specific warnings.
[1117]
XIF Revision
Shows the version of the external interface file of the Neuron C chip on the LON option.
[1118]
LON Works Revision
Shows the software version of the application program of the Neuron C chip on the LON option.
[1500]
Operating Hours
View the number of running hours of the frequency converter.
[1501]
Running Hours
View the number of running hours of the motor.
[1502]
kWh Counter
View the mains power consumption in kWh.
[1600]
Control Word
View the Control Word sent from the frequency converter via the serial communication port in hex
code.
[1601] *
Reference [Unit]
Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) in selected
unit.
[1602]
Reference %
Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) in percent.
[1603]
Status Word
Present status word
[1605]
Main Actual Value [%]
One or more warnings in a Hex code
[1609]
Custom Readout
View the user-defined readouts as defined in par. 0-30, 0-31 and 0-32.
[1610]
Power [kW]
Actual power consumed by the motor in kW.
[1611]
Power [hp]
Actual power consumed by the motor in HP.
[1612]
Motor Voltage
Voltage supplied to the motor.
[1613]
Motor Frequency
Motor frequency, i.e. the output frequency from the frequency converter in Hz.
[1614]
Motor Current
Phase current of the motor measured as effective value.
[1615]
Frequency [%]
Motor frequency, i.e. the output frequency from the frequency converter in percent.
[1616]
Torque [Nm]
Present motor load as a percentage of the rated motor torque.
[1617]
Speed [RPM]
Speed in RPM (revolutions per minute) i.e. the motor shaft speed in closed loop based on the entered
motor nameplate data, the output frequency and the load on the frequency converter.
[1618]
Motor Thermal
Thermal load on the motor, calculated by the ETR function. See also parameter group 1-9* Motor
Temperature.
[1622]
Torque [%]
Shows the actual torque produced, in percentage.
[1630]
DC Link Voltage
Intermediate circuit voltage in the frequency converter.
[1632]
BrakeEnergy/s
Present brake power transferred to an external brake resistor.
Stated as an instantaneous value.
[1633]
BrakeEnergy/2 min
Brake power transferred to an external brake resistor. The mean power is calculated continuously
for the most recent 120 seconds.
[1634]
Heatsink Temp.
Present heat sink temperature of the frequency converter. The cut-out limit is 95 ±5 oC; cutting
back in occurs at 70 ±5° C.
[1635]
Thermal Drive Load
Percentage load of the inverters
[1636]
Inv. Nom. Current
Nominal current of the frequency converter
[1637]
Inv. Max. Current
Maximum current of the frequency converter
[1638]
SL Control State
State of the event executed by the control
[1639]
Control Card Temp.
Temperature of the control card.
[1650]
External Reference
Sum of the external reference as a percentage, i.e. the sum of analog/pulse/bus.
[1652]
Feedback [Unit]
Signal value in units from the programmed digital input(s).
[1653]
Digi Pot Reference
View the contribution of the digital potentiometer to the actual reference Feedback.
[1654]
Feedback 1 [Unit]
View the value of Feedback 1. See also par. 20-0*.
[1655]
Feedback 2 [Unit]
View the value of Feedback 2. See also par. 20-0*.
[1656]
Feedback 3 [Unit]
View the value of Feedback 3. See also par. 20-0*.
[1660]
Digital Input
Displays the status of the 6 digital input terminals (18, 19, 27, 29, 32 and 33). Input 18 corresponds
to the bit at the far left. Signal low = 0; Signal high = 1
[1661]
Terminal 53 Switch Setting
Setting of input terminal 53. Current = 0; Voltage = 1.
VLT
®
AQUA Drive
Operating Instructions
8. How to programme the frequency converter
MG.20.M5.02 - VLT
®
is a registered Danfoss trademark
71