VLT
®
4000 VT
■
Installation of VLT 4006-4352
All frequency converters must be installed in a
way that ensures proper cooling.
Cooling
All Bookstyle and Compact units require a minimum
space above and below the enclosure.
Side by side/flange by flange
All frequency converters can be mounted side
by side/flange by flange.
d [mm]/in
Comments
Compact (all enclosure types)
VLT 4006 - 4011, 380-460 V
100/4.0
VLT 4006 - 4011, 525-600 V
100/4.0
Installation on a plane, vertical surface (no spacers)
VLT 4006 - 4032, 200-240 V
200/8.0
VLT 4016 - 4072, 380-460 V
200/8.0
VLT 4102 - 4122, 380-460 V
225/9.0
VLT 4016 - 4072, 525-600 V
200/8.0
Installation on a plane, vertical surface (no spacers)
VLT 4042 - 4062, 200-240 V
225/9.0
Installation on a plane, vertical surface (no spacers)
IP 54 filter mats must be changed when they are dirty.
VLT 4152 - 4352, 380-460 V
VLT 4102 - 4402, 525-600 V
225/9.0
Installation on a plane, vertical surface (spacers can be used). IP 54 filter
mats must be changed when they are dirty.
VLT 4452 - 4652, 380-460 V
225/9.0
IP 00 above and below enclosure
IP 21/IP 54 only above enclosure
MG.40.A7.22 - VLT is a registered Danfoss trademark
34