VLT
®
4000 VT
■
Line supply 3 x 380 - 460 V
According to international requirements
VLT type
4016
4022
4027
4032
4042
Output current
I
VLT,N
[A] (380-440 V)
24.0
32.0
37.5
44.0
61.0
I
VLT, MAX
(60 s) [A]
(380-440 V)
26.4
35.2
41.3
48.4
67.1
I
VLT,N
[A] (441-460 V)
21.0
27.0
34.0
40.0
52.0
I
VLT, MAX
(441-460 V)
23.1
29.7
37.4
44.0
57.2
Output
S
VLT,N
[kVA] (400 V)
17.3
23.0
27.0
31.6
43.8
S
VLT,N
[kVA] (460 V)
16.7
21.5
27.1
31.9
41.4
Typical shaft output
P
VLT,N
[kW]
11
15
18.5
22
30
Typical shaft output
P
VLT,N
[HP]
15
20
25
30
40
Max. cable cross-section
to motor and DC-bus
[mm
2
]/[AWG]
2)
16/6
16/6
16/6
16/6
35/2
Min. cable. cross-section
to motor and DC-bus
4)
[mm
2
]/[AWG]
2)
10/8
10/8
10/8
10/8
10/8
Max. input current
I
L,N
[A] (380 V)
24.0
32.0
37.5
44.0
60.0
(RMS)
I
L,N
[A] (460 V)
21.0
27.6
34.0
41.0
53.0
Max. cable, cross-section,
power
[mm
2
]/[AWG]
2)
16/6
16/6
16/6
16/6
35/2
Max. line-fuses
[A]/UL
1)
[A]
63/40
63/40
63/50
63/60
80/80
Efficiency at rated frequency
0.96
Weight NEMA 1
[lbs]
21
46
46
60
60
Weight NEMA 12
[lbs]
28
96
96
102
122
Power loss at max. load.:
W
419
559
655
768
1065
Enclosure
NEMA 1/NEMA 12
1. See section
Fuses
.
2. American Wire Gauge
3. Measured using 100 feet shielded motor cable at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on
min. cable cross-section.
MG.40.A7.22 - VLT is a registered Danfoss trademark
20