VLT
®
4000 VT
Programming
Function:
If the output frequency is above the limit, f
HIGH
,
programmed in this parameter, the display will
show a flashing FREQUENCY HIGH.
The warning functions in parameters 221-228 are
not active during ramp-up after a start command,
ramp-down after a stop command or while
stopped. The warning functions are activated when
the output frequency has reached the selected
reference. The signal outputs can be programmed
to generate a warning signal via terminal 42 or
45 and via the relay outputs.
Description of choice:
The higher signal limit of the motor frequency, f
HIGH
,
must be programmed within the normal working
range of the AFD. See drawing at parameter
221
Warning: Low current, I
LOW
.
225 Warning: Low reference, REF
LOW
(WARN. LOW REF.)
Value:
-999,999.999 - REF
HIGH
(par.226)
✭
-999,999.999
Function:
When the remote reference lies under the limit,
Ref
LOW
, programmed in this parameter, the display
shows a flashing REFERENCE LOW.
The warning functions in parameters 221-228 are
not active during ramp-up after a start command,
ramp-down after a stop command or while
stopped. The warning functions are activated when
the output frequency has reached the selected
reference. The signal outputs can be programmed
to generate a warning signal via terminal 42 or
45 and via the relay outputs.
The reference limits in parameter 226
Warning:
High reference, Ref
HIGH
, and in parameter 225
Warning: Low reference, Ref
LOW
, are only active
when remote reference has been selected.
In
Open loop mode
the unit for the reference is Hz,
while in
Closed loop mode
the unit is programmed
in parameter 415
Process units
.
Description of choice:
The lower signal limit, Ref
LOW
, of the reference must
be programmed within the normal working range of
the AFD, provided parameter 100
Configuration
has
been programmed for
Open loop
[0]. In
Closed loop
[1]
(parameter 100), Ref
LOW
must be within the reference
range programmed in parameters 204 and 205.
226 Warning: High reference, REF
HIGH
(WARN. HIGH REF.)
Value:
REF
Low
(par. 225)
- 999,999.999
✭
- 999,999.999
Function:
If the resulting reference lies under the limit, Ref
HIGH
,
programmed in this parameter, the display shows
a flashing REFERENCE HIGH.
The warning functions in parameters 221-228 are
not active during ramp-up after a start command,
ramp-down after a stop command or while stop-ped.
The warning functions are activated when the output
frequency has reached the selected reference.
The signal outputs can be programmed to
generate a warning signal via terminal 42 or
45 and via the relay outputs.
The reference limits in parameter 226 Warning:
High
reference, Ref
HIGH
, and in parameter 225
Warning:
Low reference, Ref
LOW
, are only active when remote
reference has been selected. In
Open loop
the unit
for the reference is Hz, while in
Closed loop
the unit
is programmed in parameter 415
Process units
.
Description of choice:
The upper signal limit, Ref
HIGH
,of the reference must
be programmed within the normal working range of
the AFD, provided parameter 100
Configuration
has
been programmed for
Open loop
[0]. In
Closed loop
[1]
(parameter 100), Ref
HIGH
must be within the reference
range programmed in parameters 204 and 205.
MG.40.A7.22 - VLT is a registered Danfoss trademark