VLT
®
4000 VT
Installation
■
Line Supply 3 x 525 - 600 V
According to international requirements
VLT type
4152
4202
4252
4302
4352
4402
Output current
I
VLT,N
[A] (525-550 V)
162
201
253
303
360
418
I
VLT, MAX
(60 s) [A]
(525-550 V)
178
221
278
333
396
460
I
VLT,N
[A] (551-600 V)
155
192
242
290
344
400
I
VLT, MAX
(60 s) [A]
(551-600 V)
171
211
266
319
378
440
Output
S
VLT,N
[kVA] (550 V)
154
191
241
289
343
398
S
VLT,N
[kVA] (575 V)
154
191
241
289
343
398
Typical shaft output
[kW] (550 V)
110
132
160
200
250
315
[HP] (575 V)
150
200
250
300
350
400
Max. cable cross-section
to motor
[mm
2
]
4,5
[AWG]
2,4,5
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
Max. cable cross-section
to loadsharing and brake
[mm
2
]
4,5
[AWG]
2,4,5
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
Rated input current
I
L,N
[A] (550 V)
158
198
245
299
355
408
I
L,N
[A] (575 V)
151
189
234
286
339
390
I
L,N
[A] (690 V)
155
197
240
296
352
400
Max. cable cross-section
power supply
[mm
2
]
4,5
[AWG]
2,4,5
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
Min. cable cross-section to
motor and power supply
[mm
2
]
4,5
[AWG]
2,4,5
35
2
Min. cable cross-section to
brake and loadsharing
[mm
2
]
4,5
[AWG]
2,4,5
10
8
Max. pre-fuses (mains)
[-]/UL
[A]
1
315
350
350
400
500
550
Efficiency
3
0,98
Power loss [W]
3114
3612
4293
5156
5821
6149
Weight
IP 00 [kg]
82
91
112
123
138
151
Weight
IP 21/Nema1 [kg]
96
104
125
136
151
165
Weight
IP 54/Nema12 [kg]
96
104
125
136
151
165
Enclosure
IP 00, IP 21/Nema 1 and IP 54/Nema12
1. For type of fuse see section
Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Min. cable cross-section is the minimum
allowed cross-section. Always comply with national and local regulations on min. cable cross-section.
5. Connection bolt 1 x M10 / 2 x M10 (mains and motor), connection bolt 1 x M8 / 2 x M8 (DC-bus).
MG.40.A7.22 - VLT is a registered Danfoss trademark