VLT
®
4000 VT
Installation
■
Line supply 3 x 380 - 460 V
According to international requirements
VLT type
4052
4062
4072
4102
4122
Output current
I
VLT,N
[A] (380-440 V)
73.0
90.0
106
147
177
I
VLT, MAX
(60 s) [A]
(380-440 V)
80.3
99.0
117
162
195
I
VLT,N
[A] (441-460 V)
65.0
77.0
106
130
160
I
VLT, MAX
(441-460 V)
71.5
84.7
117
143
176
Output
S
VLT,N
[kVA] (400 V)
52.5
64.7
73.4
102
123
S
VLT,N
[kVA] (460 V)
51.8
61.3
84.5
104
127
Typical shaft output
P
VLT,N
[kW]
37
45
55
75
90
Typical shaft output
P
VLT,N
[HP]
50
60
75
100
125
Max. cable cross-section
to motor and DC-bus
[mm
2
]/[AWG]
2)
35/2
50/0
50/0
120 /250
mcm
5)
120 /250
mcm
5)
Min. cable. cross-section
to motor and DC-bus
4)
[mm
2
]/[AWG]
2)
10/8
16/6
16/6
25/4
25/4
Max. input current
I
L,N
[A] (380 V)
72.0
89.0
104
145
174
(RMS)
I
L,N
[A] (460 V)
64.0
77.0
104
128
158
Max. cable, cross-section,
power
[mm
2
]/[AWG]
2)
35/2
50/0
120 /250
mcm
5)
120 /250
mcm
5)
Max. line-fuses
[A]/UL
1)
[A]
100/100
125/125
150/150
225/225
250/250
Efficiency at rated frequency
0.96
0.96
0.96
0.98
0.98
Weight NEMA 1
[lbs]
96
96
106
119
119
Weight NEMA 12
[lbs]
134
140
154
170
170
Power loss at max. load.:
W
1275
1571
1851
<1400
<1600
Enclosure
NEMA 1/NEMA 12
1. See section
Fuses.
2. American Wire Gauge.
3. Measured using 100 feet shielded motor cable at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on
min. cable cross-section.
5. DC connection 95 mm
2
/AWG 3/0.
MG.40.A7.22 - VLT is a registered Danfoss trademark
21