VLT
®
4000 VT
■
Line Supply 3 x 525 - 600 V
According to international requirements
VLT type
4102
4122
Output current
I
VLT,N
[A] (525-550 V)
113
137
I
VLT, MAX
(60 s) [A] (525-550 V)
124
151
I
VLT,N
[A] (551-600 V)
108
131
I
VLT, MAX
(60 s) [A] (551-600 V)
119
144
Output
S
VLT,N
[kVA] (550 V)
108
131
S
VLT,N
[kVA] (575 V)
108
130
Typical shaft output
[kW] (550 V)
75
90
[HP] (575 V)
100
125
Max. cable cross-section to motor
[mm
2
]
4,5
[AWG]
2,4,5
2 x 70
2 x 2/0
Max. cable cross-section to
loadsharing and brake
[mm
2
]
4,5
[AWG]
2,4,5
2 x 70
2 x 2/0
Rated input current
I
L,N
[A] (550 V)
110
130
I
L,N
[A] (575 V)
106
124
I
L,N
[A] (690 V)
109
128
Max. cable cross-section
power supply
[mm
2
]
4,5
[AWG]
2,4,5
2 x 70
2 x 2/0
Min. cable cross-section to motor and
power supply
[mm
2
]
4,5
[AWG]
2,4,5
35
2
Min. cable cross-section to brake and
loadsharing
[mm
2
]
4,5
[AWG]
2,4,5
10
8
Max. pre-fuses (mains) [-]/UL
[A]
1
200
250
Efficiency
3
0.98
Power loss [W]
2262
2662
Weight
IP 00 [kg]
82
Weight
IP 21/Nema1 [kg]
96
Weight
IP 54/Nema12 [kg]
96
Enclosure
IP 00, IP 21/Nema 1 and IP 54/Nema12
1. For type of fuse see section
Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Min. cable cross-section is the minimum
allowed cross-section. Always comply with national and local regulations on min. cable cross-section.
5. Connection bolt 1 x M10 / 2 x M10 (mains and motor), connection bolt 1 x M8 / 2 x M8 (DC-bus).
MG.40.A7.22 - VLT is a registered Danfoss trademark