Termi-
nal
Definition
Signal Signal type
Note
11
PE
–
Grounding
–
12
MCB closed/open sta-
tus
DI
Normal open: Effective by closing Standard configuration
13
14
MCB Trip
DO
Normal open: Effective by closing Standard configuration
15
16
MCB Closing Allowed
DO
Normal open: Effective by closing Standard configuration
17
18
PE
Grounding
–
19
Ready
DO
Normal open: Effective by closing Standard configuration
20
21
Running
DO
Normal open: Effective by closing Standard configuration
22
23
HV Power on
DO
Normal open: Effective by closing Standard configuration
24
25
Remote Mode/Local
Mode
DO
Normal open: Effective by closing Standard configuration
26
27
Fault
DO
Normal open: Effective by closing Standard configuration
28
29
Alarm
DO
Normal open: Effective by closing Standard configuration
30
31
MCB trip 2
DO
Normal open: Effective by closing Optional
32
33
Exciting Current
Feedback
AI
+
Standard configuration.
0–10 V voltage signal or 4–20 mA current signal
according to requirements.
34
-
35
Speed Reference (AI)
AI
+
36
-
37
Analog Output 1
AO
+
Standard configuration.
0–10 V voltage signal or 4–20 mA current signal
according to requirements.
If the analog output signal is voltage type, the
load impedance must be higher than 20 kΩ.
If the analog output signal is current type, the
load impedance must be lower than 500 Ω.
38
-
39
Analog Output 2
AO
+
40
-
41
Analog Output 3
AO
+
42
-
AQ363633621020en-000201 / 172F3117
56 | Danfoss A/S © 2021.06
Electrical Installation
VACON® 1000