AC Drive type
Low overload rating
110% (Variable torque)
High overload rating
150% (Constant tor-
que)
Cabinet dimensions
Weight
[kg]
I
L
[A]
P [kVA]
I
HD
[A]
P [kVA]
W [mm] D [mm] H [mm]
VACON1000-
ED-438-100+G2CE
438
7580
321
5550
9810
1400
2796
18200
VACON1000-
ED-560-100+G2CE
560
9690
410
7100
10610
1400
2796
21900
VACON1000-
ED-680-100+G2CE
680
11770
498
8620
11010
1400
2796
25350
Table 21: Nominal Voltage 11000 V, 54-pulse, 9 Power Cells per Phase, 50 Hz
AC Drive type
Low overload rating
110% (Variable torque)
High overload rating
150% (Constant tor-
que)
Cabinet dimensions
Weight
[kg]
I
L
[A]
P [kVA]
I
HD
[A]
P [kVA]
W [mm] D [mm] H [mm]
VACON1000-
ED-036-110+G2CE
36
680
26
490
3410
1250
2796
4400
VACON1000-
ED-050-110+G2CE
50
950
36
680
3410
1250
2796
4800
VACON1000-
ED-070-110+G2CE
70
1330
51
970
3410
1250
2796
5200
VACON1000-
ED-090-110+G2CE
90
1710
66
1250
3910
1250
2888
6550
VACON1000-
ED-100-110+G2CE
100
1900
73
1390
3910
1250
2888
6850
VACON1000-
ED-120-110+G2CE
120
2280
88
1670
3910
1250
2888
7150
VACON1000-
ED-140-110+G2CE
140
2660
102
1940
3910
1250
2888
7550
VACON1000-
ED-150-110+G2CE
150
2850
110
2090
4660
1250
2888
10600
VACON1000-
ED-180-110+G2CE
180
3420
132
2510
4660
1250
2888
10900
VACON1000-
ED-190-110+G2CE
190
3610
139
2640
4660
1250
2888
11200
VACON1000-
ED-215-110+G2CE
215
4090
157
2990
4660
1250
2888
11500
VACON1000-
ED-250-110+G2CE
250
4760
183
3480
6810
1400
2796
12950
VACON1000-
ED-305-110+G2CE
305
5810
223
4240
7010
1400
2796
14750
VACON1000-
ED-350-110+G2CE
350
6660
256
4870
7010
1400
2796
16750
AQ363633621020en-000201 / 172F3117
118 | Danfoss A/S © 2021.06