A
Output terminal
B
Heat sink
C
Handle
D
Fuse
E
Input terminal
RS
Optical fiber (receive)
TS
Optical fiber (transmit)
COM
Communication fail indicator
DRV
Drive fault indicator
UV
Undervoltage indicator
TMP
Overtemperature indicator
PWR
Power indicator
OV
Overvoltage indicator
CDL
50 V DC-link voltage indicator
3.3.3 Transformer Cabinet
The transformer cabinet includes the phase-shift transformer and its accessories.
The transformer is integrated with the cabinet base through screws for the convenience of transportation and installation. The sys-
tem default setting is that, when the transformer temperature exceeds 95°C, the system reports an excessive high temperature
alarm but does not shut down. When the temperature exceeds 110°C, the system reports an extra-high temperature fault and shuts
down.
In standalone systems, the same fan is used to cool the transformer and power cell cabinets.
e3
0b
i6
49
.1
0
A
B
C
Illustration 10: Transformer Cabinet in VACON® 1000 Standalone Systems
A
Cooling fan
B
Phase-shift transformer
C
Input current Hall sensor
AQ363633621020en-000201 / 172F3117
20 | Danfoss A/S © 2021.06
Product Overview
VACON® 1000
Operating Guide