Protections
Input overcurrent, input phase loss, input power loss, input undervolt-
age, input overvoltage, input grounding, input sequence fault, output
overcurrent, output overload, output phase loss, output grounding,
output phase imbalance, output underload, electronic motor thermal
protection, motor stall, motor reverse, motor overspeed, motor under-
speed, speed setting analog loss, encoder abnormal, external fault,
current sensor power fault, input current sampling fault, output cur-
rent sampling fault, motor winding over temperature, motor bearing
overtemperature, air filter clogged, upstream main circuit breaker ab-
normal open, HV cabinet door open, control power loss, transformer
overtemperature, PLC-DSP communication failure, cooling fan abnor-
mal, UPS undervoltage, fan power loss, transformer temperature sen-
sor loss, PLC battery voltage low, PLC-HMI communication failure, up-
stream main circuit breaker close/open failure, startup cabinet switch
abnormal open, startup cabinet switch close/open failure, cooling fan
failure
Functions
Speed ramps selection, S-curve, frequency skip, multi-point V/F, torque
boost, AVR, dead-band compensation, Jog, flying start, DC braking,
field weakening, energy saving operation, droop control, speed feed-
forward control, overvoltage prevention during deceleration, power
cell symmetrical bypass, negative sequence compensation, input un-
dervoltage derating, low voltage ride through, automatic restart, syn-
chronous transfer, multi motor parameter storage, system auto bypass
Analog input
0–10 V/4–20 mA, 2 channels
Analog output
0–10 V/4–20 mA, 4 channels
Digital input/output
7 sets input (standard, expandable)
10 sets output (standard, expandable)
Human-machine interface
7" touch screen (standard)
10" touch screen available as option
Display parameters
Target speed
Output speed
Input/output currents
Operation status indication
Communication interface
Standard: Modbus RTU
Options: PROFIBUS DP (DP-V0), DeviceNet
™
, Modbus TCP, PROFINET
I/O, EtherNet/IP
™
, EtherCAT
®
, CANopen
®
, POWERLINK, ControlNet
™
Communication protocol
MODBUS, PROFIBUS (optional)
Operation environ-
ment
Ambient temperature (opera-
tion)
0°C...+40°C (normal operation)
+40°C...+50°C (derated operation)
Ambient temperature (stor-
age/transportation)
-40°C...+70°C
Relative humidity (operation)
5–95%, no condensation
Relative humidity (storage/
transportation)
10–95%, no condensation
Altitude
<1000 m (standard)
1000–2000 m (derating)
AQ363633621020en-000201 / 172F3117
110 | Danfoss A/S © 2021.06
Specifications
VACON® 1000
Operating Guide