![background image](http://html1.mh-extra.com/html/danfoss/vacon-1000/vacon-1000_operating-manual_3533700120.webp)
AC Drive type
Low overload rating
110% (Variable tor-
que)
High overload rating
150% (Constant tor-
que)
Cabinet dimensions
Weight
[kg]
I
L
[A]
P [kVA]
I
HD
[A]
P [kVA]
W [mm] D [mm] H [mm]
VACON1000-
ED-265-024+GAUL
265
1370
194
1000
3810
1400
2796
4800
VACON1000-
ED-285-024+GAUL
285
1480
209
1080
3810
1400
2796
4900
VACON1000-
ED-305-024+GAUL
305
1580
223
1150
3810
1400
2796
5000
VACON1000-
ED-325-024+GAUL
325
1680
238
1230
4110
1400
2796
5100
VACON1000-
ED-350-024+GAUL
350
1810
256
1330
4110
1400
2796
5300
VACON1000-
ED-378-024+GAUL
378
1960
277
1430
4710
1400
2796
5850
VACON1000-
ED-408-024+GAUL
408
2120
299
1550
4710
1400
2796
6050
VACON1000-
ED-438-024+GAUL
438
2270
321
1660
4710
1400
2796
6250
VACON1000-
ED-475-024+GAUL
475
2460
348
1800
4710
1400
2796
6600
VACON1000-
ED-515-024+GAUL
515
2670
377
1950
4710
1400
2796
6900
VACON1000-
ED-560-024+GAUL
560
2900
410
2130
5010
1400
2796
7400
VACON1000-
ED-600-024+GAUL
600
3110
440
2280
5010
1400
2796
7550
VACON1000-
ED-640-024+GAUL
640
3320
469
2430
5010
1400
2796
7850
VACON1000-
ED-680-024+GAUL
680
3530
498
2580
5010
1400
2796
8250
Table 23: Nominal Voltage 3000 V, 18-pulse, 3 Power Cells per Phase, 60 Hz
AC Drive type
Low overload rating
110% (Variable tor-
que)
High overload rating
150% (Constant tor-
que)
Cabinet dimensions
Weight
[kg]
I
L
[A]
P [kVA]
I
HD
[A]
P [kVA]
W [mm] D [mm] H [mm]
VACON1000-
ED-036-030+GAUL
36
180
26
130
1210
1250
2796
2100
VACON1000-
ED-040-030+GAUL
40
200
29
150
1210
1250
2796
2125
VACON1000-
ED-050-030+GAUL
50
250
36
180
1210
1250
2796
2150
AQ363633621020en-000201 / 172F3117
120 | Danfoss A/S © 2021.06
Specifications
VACON® 1000
Operating Guide
Summary of Contents for VACON 1000
Page 1: ...Operating Guide VACON 1000 drives danfoss com...