Cable/busbar
Cable/busbar size
Terminal type
Screw type
Tightening torque (Nm)
600 kcmil
TLK400-12
M10×35
30.0–50.0
750 kcmil
TLK400-12
M10×35
30.0–50.0
Motor connection cable
9 AWG
TLK10-8
M8×25
12.0–15.0
5 AWG
TLK25-8
M8×25
12.0–15.0
2 AWG
TLK35-8
M8×25
12.0–15.0
2/0 AWG
TLK70-8
M8×25
12.0–15.0
3/0 AWG
TLK95-10
M10×35
30.0–50.0
4/0 AWG
TLK120-10
M10×35
30.0–50.0
250 kcmil
TLK150-10
M10×35
30.0–50.0
300 kcmil
TLK185-10
M10×35
30.0–50.0
400 kcmil
TLK240-10
M10×35
30.0–50.0
600 kcmil
TLK400-12
M10×35
30.0–50.0
750 kcmil
TLK400-12
M10×35
30.0–50.0
Grounding connection between cabinets
75 mm
2
N/A
M8×25
12.0–15.0
120 mm
2
N/A
M8×25
12.0–15.0
200 mm
2
N/A
M8×25
12.0–15.0
300 mm
2
N/A
M8×25
12.0–15.0
System grounding cable
100 mm
2
TLK120-8
M8×20
12.0–15.0
11.4 Replacement Fuses
Table 31: Fuses in the Power Cell Cabinet for Standalone Type (Power Cell Current ≤215 A)
Power cell current rating
Fuse model
Fuse rating
36 A
170M1367
700 V AC, 100 A
170M2614
700 V AC, 100 A
170M4810
1000 V AC, 100 A
50 A
170M1368
700 V AC, 125 A
170M2615
700 V AC, 125 A
170M4811
1000 V AC, 125 A
70 A
170M1369
700 V AC, 160 A
170M2616
700 V AC, 160 A
170M4812
1000 V AC, 160 A
100 A
170M1371
700 V AC, 250 A
170M2618
700 V AC, 250 A
AQ363633621020en-000201 / 172F3117 | 135