FCM 300 Series
MG.03.B6.2G - VLT is a registered Danfoss trademark
Selection of Setup,
Selection of Setup,
Selection of Setup,
Selection of Setup,
Selection of Setup,
enables a choice of one of the
two Setups; however, this presupposes that
parameter 004 has been set to
Multi Setup.
Catch-up/Slow-down
Catch-up/Slow-down
Catch-up/Slow-down
Catch-up/Slow-down
Catch-up/Slow-down
is selected if the reference
value is to be increased or reduced by a
programmable percentage value set in parameter
219.
Slow-down
Catch-up
Unchanged speed
0
0
Reduced by %-value
1
0
Increased by %-value
0
1
Reduced by %-value
1
1
Preset reference
Preset reference
Preset reference
Preset reference
Preset reference
enables a choice of one of the
two preset references, in accordance with the table
in parameter 215 and 216. To be active,
Preset
reference, on
has to be selected.
Preset reference, on
Preset reference, on
Preset reference, on
Preset reference, on
Preset reference, on
is used for shifting between
external reference and preset reference. It is
assumed that
External/preset
[2] has been selected
in parameter 214. Logic '0' = external references
active; logic '1' = one of the two preset references
is active.
Precise stop
Precise stop
Precise stop
Precise stop
Precise stop
corrects the ramp-down time to
obtain a high repetitive accuracy of the stopping
point.
Pulse reference
Pulse reference
Pulse reference
Pulse reference
Pulse reference
is selected if a pulse sequence
(frequency) of 0 Hz is used, corresponding to Ref
MIN
,
parameter 204. The frequency is set in parameter
327, corresponding to Ref
MAX
.
Pulse feedback
Pulse feedback
Pulse feedback
Pulse feedback
Pulse feedback
is selected if a pulse sequence
(frequency) is selected as a feedback signal.
Analog reference
Analog reference
Analog reference
Analog reference
Analog reference
is selected to enable change of
reference by means of an analog reference signal.
If other inputs are connected, these are summed,
taking account of their signs.
Analog feedback
Analog feedback
Analog feedback
Analog feedback
Analog feedback
is selected if closed loop
regulation with an analog signal is used.
Reset and start
Reset and start
Reset and start
Reset and start
Reset and start
is used for activating start at the
same time as reset.
Scaling of the input signal is effected in parameters
338 and 339.
NOTE!
NOTE!
NOTE!
NOTE!
NOTE!
If
Reference
or
Feedback
has been selected on
more than one terminal, these signals will be
summed with signs.
336 Terminal 1, min. scaling
(AI 1 SCALE LOW)
Settings:
0.0 - 20.0 mA
[0 - 200]
H,I
4.0 mA
[40]
★
0.0 mA
[0]
Function:
This parameter determines the value of the
reference signal that is to correspond to the
minimum reference value set in parameter 204.
If the
Time-out
function of parameter 317 is to be
used, the setting must be > 2 mA.
Description of choice:
Set the desired current value.
337 Terminal 1, max. scaling
(AI 1 SCALE HIGH)
Setting:
0.0 - 20.0 mA
[0 - 200]
★
20.0 mA
[200]
Function:
This parameter sets the value of the reference signal
that is to correspond to the maximum reference
value set in parameter 205.
Description of choice:
Set the desired current value.
✭
=
General factory setting - also applying to spare part unit, H
H
H
H
H = HVAC setting, IIIII = Industrial setting, ( ) = parameter
window text. [ ] = value for use in communication via serial communication port
Parameter Group 3: Inputs and Outputs
11-5
Example:
Terminal
Freeze ref./
2-5
2-5
Freeze output
No speed change
0
0
1
Speed down
0
1
1
Speed up
1
0
1
Speed down
1
1
1