FCM 300 Series
MG.03.B6.2G - VLT is a registered Danfoss trademark
Function:
The choice in this parameter defines the Setup
number you want to control the functions of the
FCM 300.
All parameters can be programmed in two individual
parameter Setups, Setup 1 and Setup 2. In
addition, there is a pre-programmed Setup, called
Factory Setup, that cannot be modified.
Description of choice:
Factory Setup
[0] contains the factory data and can
be used as a data source if the other Setups are to
be returned to a known state.
Parameters 005 and 006 allow copying from one
Setup to the other.
Setups
1 [1] and 2 [2] are two individual Setups that
can be selected as required.
Multi-Setup
[5] is used if remote-mounting switching
between Setups is desired. Terminals 2, 3, 4, and 5
as well as the serial communication port can be
used for switching between Setups.
005 Programming Setup (EDIT SETUP)
Settings:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
✭
Active Setup (ACTIVE SETUP)
[5]
Function:
The choice is of the Setup in which programming
(change of data) is to occur during operation. It is
possible to program the two Setups independently
of the Setup selected as the Active Setup (selected
in parameter 004).
Description of choice:
The Factory Setup
[0] contains the factory data and
can be used as a data source if the other Setups
are to be returned to a known state.
004 Active Setup (ACTIVE SETUP)
Settings:
Factory Setup (FACTORY SETUP)
[0]
✭
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
Multi Setup (MULTI SETUP)
[5]
✭
=
General factory setting - also applying to spare part unit, H
H
H
H
H = HVAC setting, IIIII = Industrial setting, ( ) = parameter
window text. [ ] = value for use in communication via serial communication port
Parameter Group 0: Operation & Display
003 Local reference
(LOCAL REFERENCE)
Settings:
Par 013 set for [1] or [2]:
0 - f
MAX
✭
000.000
Par 013 set for [3] or [4] and par. 203 = [0] set for
:
Ref
MIN
- Ref
MAX
✭
000.000
Par 013 set for [3] or [4] and par. 203 = [1] set for:
-Ref
MAX
- + Ref
MAX
✭
000.000
Function:
This parameter allows manual setting of the desired
reference value (speed or reference for the selected
configuration, depending on the choice made in
parameter 013).
The unit follows the configuration selected in
parameter 100, provided that
Process regulation,
closed loop
[3] has been selected.
Description of choice:
Local
[1] must be selected in parameter 002 for this
parameter to be used.
The set value is saved in the case of a voltage drop-
out, see parameter 019.
In this parameter Data Change Mode is not exited
automatically (after time out).
Local reference cannot be set via the serial
communication port.
Warning:
Since the value set is remembered
after the power has been cut, the motor
may start without warning when the
power is reinstated; if parameter 019 is changed to
Auto restart
, use
saved ref.
[0].
8-3