FCM 300 Series
MG.03.B6.2G - VLT is a registered Danfoss trademark
Parameters
Range/number
Function
of settings/value
Factory setting
Parameter No.
Language
6
English
Parameter 001
Local/remote control
2
Remote control
Parameter 002
Local reference
000.000
Parameter 003
Active Setup
4
Setup 1
Parameter 004
Programming Setup
4
Active setup
Parameter 005
Copying of Setups
4
No copying
Parameter 006
LCP copy
4
No copying
Parameter 007
Display scaling of motor frequency
100
Parameter 008
Display line 2
24
Frequency [Hz]
Parameter 009
Display line 1.1
Reference [%]
Parameter 010
Display line 1.2
Motor current [A]
Parameter 011
Display line 1.3
Power [kW]
Parameter 012
Local control/configaration
5
LCP digital control/par. 100 Parameter 013
Local stop
2
Possible
Parameter 014
Local jog
2
Not possible
Parameter 015
Local reversing
2
Not possible
Parameter 016
Local reset of trip
2
Possible
Parameter 017
Lock for data change
2
Not locked
Parameter 018
Operating state at power up, local c. 3
Forced stop, use saved ref. Parameter 019
Configuration
2
Speed, open loop mode
Parameter 100
Torque characteristics
4
Constant torque
Parameter 101
Motor power
XX.XX kW - dep. on unit
Parameter 102
Motor voltage
XX.XX V - dep. on unit
Parameter 103
Motor frequency
XX.X Hz - dep. on unit
Parameter 104
Motor current
XX.XX A - dep. on unit
Parameter 105
Rated motor speed
XX rpm - dep. on unit
Parameter 106
DC braking time
0.0 (off) - 60.0 sec.
10.0 sec.
Parameter 126
DC brake cut-in frequency
0.0 Hz - f
MAX
0.0 Hz
Parameter 127
Motor thermal protection
2
Disable
Parameter 128
DC braking voltage
0 - 100 %
0 %
Parameter 132
Start voltage
0.00 - 100.00 V
Motor dependent
Parameter 133
Start compensation
0.0 - 300.0 %
100.0 %
Parameter 134
U/f ratio
0.00 - 20.00 V/Hz
Motor dependent
Parameter 135
Slip compensation
-500.0 - +500.0 %
100.0 %
Parameter 136
DC holding voltage
0 - 100 %
0 %
Parameter 137
Brake cut out frequency
0.5 - 132 Hz
3.0 Hz
Parameter 138
Brake cut in frequency
0.5 - 132 Hz
3.0 Hz
Parameter 139
Rotation direction
3
Only clockwise 0 - 132 Hz Parameter 200
Min. output frequency (f
MIN
)
0.0 Hz - f
MAX
0.0 Hz
Parameter 201
Max. output frequency (f
MAX
)
f
MIN -
f
RANGE
f
RANGE
(132 Hz)
Parameter 202
Reference/feedback range
Min. - max./-max.- +max. Min. - Max.
Parameter 203
Minimum reference
-100,000.000 - Ref
MAX
0.000
Parameter 204
Maximum reference
Ref
MIN
- 100,000.000
50.000
Parameter 205
Ramp-up time 1
0.05 - 3600.00 sec.
3.00 sec.
Parameter 207
Ramp-down time 1
0.05 - 3600.00 sec.
3.00 sec.
Parameter 208
Jog ramp time
0.05 - 3600.00 sec.
3.00 sec.
Parameter 211
Quick stop ramp-down time
0.05 - 3600.00 sec.
3.00 sec.
Parameter 212
Jog frequency
0 Hz - f
MAX
10.0 Hz
Parameter 213
Reference function
2
Sum
Parameter 214
Parameters for programming, controlling, and monitoring the FCM 300 via serial communication or PC.
References and limitsReferences and limitsReferences and limitsReferences and limitsReferences and limits
Load and motorLoad and motorLoad and motorLoad and motorLoad and motor
Operation and displayOperation and displayOperation and displayOperation and displayOperation and display
■
Standard Parameter Setting
19-2