FCM 300 Series
MG.03.B6.2G - VLT is a registered Danfoss trademark
✭
=
General factory setting - also applying to spare part unit, H
H
H
H
H = HVAC setting, IIIII = industrial setting,
( ) = display text [ ] = value for use in communication via serial communication port
Parameter Group 0: Operation & Display
019 Operating state at power up, local
control (POWER UP ACTION)
Value:
H
Auto restart, use saved ref.(AUTO RESTART)
[0]
✭
Forced stop, use saved ref. (LOCAL=STOP)
[1]
Forced stop, set ref. to 0
(LOCAL=STOP, REF=0)
[2]
Function:
Setting of the desired operating mode when the
mains voltage is reconnected.
This function can only be active in connection with
Local control
[1] in parameter 002.
Description of choice:
Auto restart, use saved ref.
[0] is selected if the unit
is to start up with the same local reference (set in
parameter 003) and the same start/stop conditions
(given via the [START/STOP] keys) that the FCM
300 had before it was switched off.
Forced stop, use saved ref.
[1] is used if the unit is
to remain stopped when the mains voltage is
connected, until the [START] key is pressed. After
the start command, the local reference used is set
in parameter 003.
018 Lock for data change
(DATA CHANGE LOCK)
Value:
✭
Not locked (NOT LOCKED)
[0]
Locked (LOCKED)
[1]
Function:
In this parameter, the software can "lock" the
control, which means that data changes cannot be
made via LCP 2 (however, this is still possible via the
serial communication port).
Description of choice:
If
Locked
[1] is selected, data changes cannot be
made.
8-8
Forced stop, set ref. to 0
[2] is selected if the unit is
to remain stopped when the mains voltage is
connected. Local reference (parameter 003) is
reset.
NOTE!
In remote controlled operation (parameter 002), the
start/stop condition at power up will depend on the
external control signals. If
Latched start
is selected
in parameter 332-335, the motor will remain
stopped at power up.