FCM 300 Series
MG.03.B6.2G - VLT is a registered Danfoss trademark
Setups
1
[1] and 2 [2] are individual Setups which
can be used as required. They can be programmed
freely, regardless of the Setup selected as the Active
Setup and thus controlling the functions of the FCM
300.
NOTE!
If a general change of data or a copying to the
Active Setup is effected, this immediately affects the
functioning of the unit.
006 Copying of Setups (SETUP COPY)
Settings:
✭
No copying (NO COPY)
[0]
Copy to Setup 1 from # (COPY TO SETUP 1)
[1]
Copy to Setup 2 from # (COPY TO SETUP 2)
[2]
Copy to Setup all from # (COPY TO ALL)
[5]
# = the Setup selected in parameter 005
Function:
A copy is made from the Setup selected in
parameter 005 to one of the other Setups or to all
the other Setups simultaneously.
NOTE!
Copying is only possible in Stop Mode (motor
stopped on a Stop command).
Copying will take max. 3 seconds and has ended
when parameter 006 has returned to value 0.
007 LCP copy (LCP COPY)
Settings:
✭
No copying (NO COPY)
[0]
Upload all parameters (UPLOAD ALL PARAM) [1]
Download all parameters (DOWNLOAD ALL)
[2]
Download power-independent par.
(DOWNLOAD SIZE INDEP.)
[3]
Function:
Parameter 007 is used if it is desired to use the
integrated copying function of the control panel. You
can therefore easily copy parameter value(s) from
one FCM 300 to another.
Description of choice:
Select
Upload all parameters
[1] if all parameter
values are to be transmitted to the control panel.
Select
Download all parameters
[2] if all transmitted
parameter values are to be copied to the FCM 300
on which the control panel has been mounted.
Select
Download power-independent par.
[3] if only
the power-independent parameters are to be
downloaded. This is used if downloading to a FCM
300 that has a different rated power than the one
from where the parameter Setup originates.
NOTE!
Uploading/Downloading can only be carried out in
the Stop mode and only between units with the
same database version (see par. 626 value)
008 Display scaling of motor frequency
(FREQUENCY SCALE)
Settings:
0.01 - 100.00
[ - 10000]
✭
1.00
[100]
Function:
This parameter chooses the factor to be multiplied
by the motor frequency, f
M
, for presentation in the
display, when parameters 009-012 have been set
for Frequency x Scaling [5].
Description of choice:
Set the desired scaling factor.
009 Display line 2 (DISPLAY LINE 2)
Settings:
None
[0]
Reference [%] (REFERENCE [%])
[1]
Reference [unit] (REFERENCE [UNIT])
[2]
Feedback [unit] (FEEDBACK [UNIT])
[3]
✭
Frequency [Hz] (FREQUENCY [Hz])
[4]
Frequency x Scaling [-] (FREQUENCY X SCALE)
[5]
Motor current [A] (MOTOR CURRENT [A])
[6]
Torque [%] (TORQUE [%])
[7]
Power [kW] (POWER [kW])
[8]
Power [HP] (POWER [hp] [US])
[9]
Motor voltage [V] (MOTOR VOLTAGE [V])
[11]
8-4
✭
=
General factory setting - also applying to spare part unit, H
H
H
H
H = HVAC setting, IIIII = Industrial setting,
( ) = display text [ ] = value for use in communication via serial communication port
Parameter Group 0: Operation & Display