AK-PC 781A
Capacity
controller RS8HE202 © Danfoss 2017-07
35
4
7
6
5
Planning table
The table helps you establish whether there are enough
inputs and outputs on the basic controller.
If there are not enough of them, the controller must be
extended by one or more of the mentioned extension
modules.
Note down the connections you will require and add
them up
A
nalog input signal
Example
O
n/off v
oltage signal
Example
O
n/off v
oltage signal
Example
O
n/O
ff output signal
Example
A
nalog output signal 0-10
V
St
epper output
Example
Limita
tions
Analog inputs
Temperature sensors, Ss, Sd, Sc3, S4, S7, Stw.., Shr.., Sgc
9
Extra temperature sensor / separate thermostats /PI-regulation
1
Pressure transmitters, P0, Pc, Pctrl. Prec / separate pressostats
5
P = Max. 5 / module
Voltage signal from other regulation, separate signals
Heat recovery via thermostat
On/off inputs
Contact
24 V
230 V
Safety circuits, common for all compressors
1
Max.1
Safety circuits, Oil pressure
Max. 1/ Comp.
Safety circuits, comp. Motor protection
Safety circuits, comp. Motor temp.
Safety circuits, comp. High pres. thermostat
Safety circuits, comp. High pres. pressostat
Safety circuits, general for each compressor
4
Safety circuits, condenser fans, frequency converter
Max. 1/ fan
Safety circuits, flow switch
2
External start/stop
1
LT release input / MT request input / IT release input
Night setback of suction pressure
Separate alarm functions via DI
1
Load shedding
Start of Heat recovery
1
1
Liquid level, Oil level
8
Pulse reset of oil management
1
On/off outputs
Compressors, motors
4
Unloaders
Fan motors, circulation pumps
3
Alarm relay, I'm alive relay
Inject ON
Max. 1
Separate thermostat and pressostat functions and voltage measure-
ments
1
Max. 5+5+5
Heat recovery function via thermostat
Max.1
Liquid injection in suction line / heat exchanger. Heat gas dump
Max.1
MT release output / LT request output / IT on-outp. / IT release outp.
Solenoid valve for Oil.
5
3-way valve
3
Analog control signal, 0-10 V
Frequency converter, Compressor, fans, pumps, valves etc.
5
Valves with stepper motor. Parallel valves, if applicable
1
Sum of connections for the regulation
27
0
8
16
5+1 Sum = max. 120
Number of connections on a controller module
11
11
0
0
0
0
8
8
0
0
0
Missing connections, if applicable
16
-
8
8
5+1
The missing connections to be supplied by one or more extension modules:
Sum of power
AK-XM 101A (8 analog inputs)
___ pcs. á 2 VA = __
AK-XM 102A (8 digital low voltage inputs)
___ pcs. á 2 VA = __
AK-XM 102B (8 digital high voltage outputs)
1
___ pcs. á 2 VA = __
AK-XM 103A (4 analog inputs, 4 analog outputs)
1
1
___ pcs. á 2 VA = __
AK-XM 204A / B (8 relay outputs)
___ pcs. á 5 VA = __
AK-XM 205A / B (8 analog inputs. + 8 relay output)
1
1
___ pcs. á 5 VA = __
AK-XM 208C (8 analog 4 stepper outputs)
1
1
___ pcs. á 5 VA = __
AK_OB 110 (2 analog outputs)
1
___ pcs. á 0 VA = 0
1 pcs. á 8 VA = 8
Sum =
Sum = max. 32 VA
The example:
None of the 3 limita
tions ar
e ex
ceeded => OK
Summary of Contents for AK-PC 781A
Page 39: ...AK PC 781A Capacity controller RS8HE202 Danfoss 2017 07 39 Example continued ...
Page 42: ...42 Capacity controller RS8HE202 Danfoss 2017 07 AK PC 781A ...
Page 90: ...90 Capacity controller RS8HE202 Danfoss 2017 07 AK PC 781A ...
Page 133: ...AK PC 781A Capacity controller RS8HE202 Danfoss 2017 07 133 ...