38
Capacity
controller RS8HE202 © Danfoss 2017-07
AK-PC 781A
11
Signal
Module
Point
Terminal
Active at
Compressor 1 Gen. Safety
4
1 (DI 1)
1 - 2
Open
Compressor 2 Gen. Safety
2 (DI 2)
3 - 4
Open
Compressor 3 Gen. Safety
3 (DI 3)
5 - 6
Open
Compressor 4 Gen. Safety
4 (DI 4)
7 - 8
Open
Start/stop heat recovery hr
5 (DI 5)
9 - 10
Closed
All compressors common safety
6 (DI 6)
11 - 12
Open
Flow switch FStw
7 (DI 7)
13 - 14
Open
Flow switch FShr
8 (DI 8)
15 - 16
Open
Signal
Module
Point
Terminal
Signal type
Temp. gas cooler outlet Sgc
5
1 (AI 1)
1 - 2
Pt 1000
Temp. by-pased gas Shp
2 (AI 2)
3 - 4
Pt 1000
Start/stop heat recovery tw
3 (AI 3)
5 - 6
Closed
Gas cooler pressure Pgc
4 (AI 4)
7 - 8
AKS 2050-159
Speed control, compressor
5 (AO 1)
9 - 10
0 - 10 V
Speed control, gas cooler fan
6 (AO 2)
11 - 12
0 - 10 V
Speed control, pump - tw
7 (AO 3)
13 - 14
0 - 10 V
Speed control, pump - hr
8 (AO 4)
15 - 16
0 - 10 V
Connection diagram
Drawings of the individual modules may be
ordered from Danfoss.
Format = dwg and dxf.
You may then yourself write the module
number in the circle and draw the individual
connections.
The supply voltage for the pressure
transmitter should be taken from
the same module that receives the
pressure signal.
Summary of Contents for AK-PC 781A
Page 39: ...AK PC 781A Capacity controller RS8HE202 Danfoss 2017 07 39 Example continued ...
Page 42: ...42 Capacity controller RS8HE202 Danfoss 2017 07 AK PC 781A ...
Page 90: ...90 Capacity controller RS8HE202 Danfoss 2017 07 AK PC 781A ...
Page 133: ...AK PC 781A Capacity controller RS8HE202 Danfoss 2017 07 133 ...