6.1.6 Tips and Tricks
*
For the majority of ADAP-KOOL applications the Quick Menu, Quick Set-up and Function Set-up provides the simplest
and quickest access to all the typical parameters required.
*
Whenever possible, performing an AMA, will ensure best shaft performance
*
Contrast of the display can be adjusted by pressing [Status] and [
▲
] for darker display or by pressing [Status] and [
▼
]
for brighter dispaly
*
Under [Quick Menu] and [Changes Made] all parameters that have been changed from factory settings are displayed
*
Press and hold [Main Menu] key for 3 seconds for access to any parameter
*
For service purposes it is recommended to copy all parameters to the LCP, see par 0-50 for further information
Table 6.1 Tips and tricks
6.1.7 Quick Transfer of Parameter Settings when Using GLCP
Once the set-up of a frequency converter is complete, it is recommended to store (backup) the parameter settings in the
GLCP or on a PC via MCT 10 Set-up Software Tool.
WARNING
Stop the motor before performing any of these operations.
Data storage in LCP:
1.
Go to
0-50 LCP Copy
2.
Press the [OK] key
3.
Select “All to LCP”
4.
Press the [OK] key
All parameter settings are now stored in the GLCP indicated by the progress bar. When 100% is reached, press [OK].
The GLCP can now be connected to another frequency converter and the parameter settings copied to this frequency
converter.
Data transfer from LCP to Frequency converter:
1.
Go to
0-50 LCP Copy
2.
Press the [OK] key
3.
Select “All from LCP”
4.
Press the [OK] key
The parameter settings stored in the GLCP are now transferred to the frequency converter indicated by the progress bar.
When 100% is reached, press [OK].
6.1.8 Initialisation to Default Settings
There are two ways to initialise the frequency converter to default: Recommended initialisation and manual initialisation.
Please be aware that they have different impact according to the below description.
Recommended initialisation (via
14-22 Operation Mode
)
1.
Select
14-22 Operation Mode
2.
Press [OK]
3.
Select “Initialisation” (for NLCP select “2”)
4.
Press [OK]
How to Operate the Frequenc...
ADAP-KOOL
®
Drive Operating Instructions
52
MG.11.L4.02 - ADAP-KOOL
®
Drive