3-13 Reference Site
Option:
Function:
Select which reference site to activate.
[0]
*
Linked to
Hand / Auto
Use local reference when in Hand mode; or
remote reference when in Auto mode.
[1]
Remote
Use remote reference in both Hand mode
and Auto mode.
[2]
Local
Use local reference in both Hand mode and
Auto mode.
NOTE
When set to Local [2], the frequency
converter will start with this setting
again following a 'power down'.
3-15 Reference 1 Source
Option:
Function:
Select the reference input to be used
for the first reference signal.
,
3-16 Reference
2 Source
and
3-17 Reference 3 Source
define up to three different reference
signals. The sum of these reference
signals defines the actual reference.
This parameter cannot be adjusted
while the motor is running.
[0]
No function
[1]
*
Analog input 53
[2]
Analog input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital pot.meter
[21]
Analog input X30/11
[22]
Analog input X30/12
[23]
Analog Input X42/1
[24]
Analog Input X42/3
[25]
Analog Input X42/5
[30]
Ext. Closed Loop 1
[31]
Ext. Closed Loop 2
[32]
Ext. Closed Loop 3
6-10 Terminal 53 Low Voltage
Range:
Function:
0.07 V
*
[0.00 - par.
6-11 V]
Enter the low voltage value. This analog
input scaling value should correspond to
the low reference/feedback value set in
6-14 Terminal 53 Low Ref./Feedb. Value
6-11 Terminal 53 High Voltage
Range:
Function:
10.00 V
*
[par. 6-10 -
10.00 V]
Enter the high voltage value. This
analog input scaling value should
correspond to the high reference/
6-11 Terminal 53 High Voltage
Range:
Function:
feedback value set in
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A
*
[-999999.999 -
999999.999 N/A]
Enter the analog input scaling
value that corresponds to the
low voltage/low current set in
and
6-12 Terminal 53 Low
Current
.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
100.000
N/A
*
[-999999.999 -
999999.999 N/A]
Enter the analog input scaling
value that corresponds to the
high voltage/high current
and
6-13 Terminal 53 High Current
.
6-20 Terminal 54 Low Voltage
Range:
Function:
0.07 V
*
[0.00 - par.
6-21 V]
Enter the low voltage value. This analog
input scaling value should correspond to
the low reference/feedback value, set in
6-24 Terminal 54 Low Ref./Feedb. Value
6-21 Terminal 54 High Voltage
Range:
Function:
10.00 V
*
[par. 6-20 -
10.00 V]
Enter the high voltage value. This
analog input scaling value should
correspond to the high reference/
feedback value set in
6-22 Terminal 54 Low Current
Range:
Function:
4.00
mA
*
[0.00 -
par. 6-23
mA]
Enter the low current value. This reference
signal should correspond to the low
reference/feedback value, set in
6-24 Terminal 54 Low Ref./Feedb. Value
. The
value must be set at >2 mA in order to
activate the Live Zero Time-out Function in
6-01 Live Zero Timeout Function
.
6-23 Terminal 54 High Current
Range:
Function:
20.00 mA
*
[par. 6-22 -
20.00 mA]
Enter the high current value
corresponding to the high reference/
How to Programme the Frequ...
ADAP-KOOL
®
Drive Operating Instructions
MG.11.L4.02 - ADAP-KOOL
®
Drive
71