6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
-1.000 N/A
*
[-999999.999 -
999999.999 N/A]
Enter the analog input scaling
value that corresponds to the
low voltage/low current value
set in
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
Application
Dependent
*
[-999999.999 -
999999.999 N/A]
Enter the analog input
scaling value that
corresponds to the high
voltage/high current value
set in
.
6-50 Terminal 42 Output
Option:
Function:
Select the function of Terminal 42 as
an analog current output. A motor
current of 20 mA corresponds to
I
max
.
[0]
*
No operation
[100]
*
Output frequency
: 0 - 100 Hz, (0-20 mA)
[101]
Reference
: Minimum reference - Maximum
reference, (0-20 mA)
[102]
Feedback
: -200% to +200% of
20-14 Maximum
Reference/Feedb.
, (0-20 mA)
[103]
Motor current
: 0 - Inverter Max. Current (
16-37 Inv.
Max. Current
), (0-20 mA)
[104]
Torque rel to limit
: 0 - Torque limit (
4-16 Torque Limit
Motor Mode
), (0-20 mA)
[105]
Torq relate to
rated
: 0 - Motor rated torque, (0-20 mA)
[106]
Power
: 0 - Motor rated power, (0-20 mA)
[107]
*
Speed
: 0 - Speed High Limit (
4-13 Motor
Speed High Limit [RPM]
4-14 Motor Speed High Limit [Hz]
(0-20 mA)
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop 1
: 0 - 100%, (0-20 mA)
[114]
Ext. Closed Loop 2
: 0 - 100%, (0-20 mA)
[115]
Ext. Closed Loop 3
: 0 - 100%, (0-20 mA)
[130]
Output freq.
4-20mA
: 0 - 100 Hz
[131]
Reference 4-20mA
: Minimum Reference - Maximum
Reference
6-50 Terminal 42 Output
Option:
Function:
[132]
Feedback 4-20mA
: -200% to +200% of
20-14 Maximum
Reference/Feedb.
[133]
Motor cur. 4-20mA : 0 - Inverter Max. Current (
16-37 Inv.
Max. Current
)
[134]
Torq.% lim 4-20
mA
: 0 - Torque limit (
4-16 Torque Limit
Motor Mode
)
[135]
Torq.% nom
4-20mA
: 0 - Motor rated torque
[136]
Power 4-20mA
: 0 - Motor rated power
[137]
Speed 4-20mA
: 0 - Speed High Limit (4-13 and
4-14)
[138]
Torque 4-20mA
[139]
Bus ctrl.
: 0 - 100%, (0-20 mA)
[140]
Bus ctrl. 4-20 mA
: 0 - 100%
[141]
Bus ctrl t.o.
: 0 - 100%, (0-20 mA)
[142]
Bus ctrl t.o.
4-20mA
: 0 - 100%
[143]
Ext. CL 1 4-20mA
: 0 - 100%
[144]
Ext. CL 2 4-20mA
: 0 - 100%
[145]
Ext. CL 3 4-20mA
: 0 - 100%
[150]
Max Out Fr 4-20
mA
NOTE
Values for setting the Minimum Reference is found in open
loop
and for closed loop
20-13 Minimum Reference/Feedb.
- values for maximum
reference for open loop is found in
and for closed loop
20-14 Maximum Reference/
Feedb.
.
6-51 Terminal 42 Output Min Scale
Range:
Function:
0.00 %
*
[0.00 -
200.00 %]
Scale for the minimum output (0 or 4
mA) of the analogue signal at terminal
42.
Set the value to be the percentage of
the full range of the variable selected in