5 Electrical Installation
5.1 How
to
Connect
5.1.1 Cables General
NOTE
For the AKDHigh Power series mains and motor connections, please see the ADAP-KOOL
®
Drive AKD102High Power
Operating Instructions, MG.11.Ox.yy.
NOTE
Cables General
Always comply with national and local regulations on cable cross-sections.
Details of terminal tightening torques.
Power (kW)
Torque (Nm)
Enclo-
sure
200-240
V
380-480
V
Line
Motor
DC
connection
Brake
Earth
Relay
A2
1.1 - 3.0
1.1 - 4.0
1.8
1.8
1.8
1.8
3
0.6
A3
3.7
5.5 - 7.5
1.8
1.8
1.8
1.8
3
0.6
A4
1.1 - 2.2
1.4 - 4
1.8
1.8
1.8
1.8
3
0.6
A5
1.1 - 3.7
1.1 - 7.5
1.8
1.8
1.8
1.8
3
0.6
B1
5.5 - 11
11 - 18.5
1.8
1.8
1.5
1.5
3
0.6
B2
-
15
22
30
2.5
4.5
2.5
4.5
3.7
3.7
3.7
3.7
3
3
0.6
0.6
C1
18.5 - 30
37 - 55
10
10
10
10
3
0.6
C2
37
45
75
90
14
24
14
24
14
14
14
14
3
3
0.6
0.6
Table 5.1 Tightening of terminals
Electrical Installation
ADAP-KOOL
®
Drive Operating Instructions
MG.11.L4.02 - ADAP-KOOL
®
Drive
25