9.1.1 Mains Supply 3 x 380 - 480 VAC
Mains Supply 3 x 380 - 480 VAC - Normal overload 110% for 1 minute
Frequency converter
Typical Shaft Output [kW]
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P4K0
4
P5K5
5.5
P7K5
7.5
Typical Shaft Output [HP] at 460 V
1.5
2.0
2.9
4.0
5.3
7.5
10
IP 20 / Chassis
A2
A2
A2
A2
A2
A3
A3
IP 21 / NEMA 1
IP 55 / NEMA 12
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
IP 66 / NEMA 12
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
Output current
Continuous
(3 x 380-440 V) [A]
3
4.1
5.6
7.2
10
13
16
Intermittent
(3 x 380-440 V) [A]
3.3
4.5
6.2
7.9
11
14.3
17.6
Continuous
(3 x 440-480 V) [A]
2.7
3.4
4.8
6.3
8.2
11
14.5
Intermittent
(3 x 440-480 V) [A]
3.0
3.7
5.3
6.9
9.0
12.1
15.4
Continuous kVA
(400 V AC) [kVA]
2.1
2.8
3.9
5.0
6.9
9.0
11.0
Continuous kVA
(460 V AC) [kVA]
2.4
2.7
3.8
5.0
6.5
8.8
11.6
Max. cable size:
(mains, motor, brake)
[mm
2
/ AWG]
2)
4/10
Max. input current
Continuous
(3 x 380-440 V ) [A]
2.7
3.7
5.0
6.5
9.0
11.7
14.4
Intermittent
(3 x 380-440 V ) [A]
3.0
4.1
5.5
7.2
9.9
12.9
15.8
Continuous
(3 x 440-480 V) [A]
2.7
3.1
4.3
5.7
7.4
9.9
13.0
Intermittent
(3 x 440-480 V) [A]
3.0
3.4
4.7
6.3
8.1
10.9
14.3
Max. pre-fuses
1)
[A]
10
10
20
20
20
32
32
Environment
Estimated power loss
at rated max. load [W]
4)
58
62
88
116
124
187
255
Weight enclosure IP20 [kg]
4.8
4.9
4.9
4.9
4.9
6.6
6.6
Weight enclosure IP21 [kg]
Weight enclosure IP55 [kg]
13.5
13.5
13.5
13.5
13.5
14.2
14.2
Weight enclosure IP66 [kg]
13.5
13.5
13.5
13.5
13.5
14.2
14.2
Efficiency
3)
0.96
0.97
0.97
0.97
0.97
0.97
0.97
Specifications
ADAP-KOOL
®
Drive Operating Instructions
118
MG.11.L4.02 - ADAP-KOOL
®
Drive
9
9