4.2.2 Safety Requirements of Mechanical Installation
WARNING
Pay attention to the requirements that apply to integration and field mounting kit. Observe the information in the list to
avoid serious injury or equipment damage, especially when installing large units.
NOTE
The frequency converter is cooled by means of air circulation.
To protect the unit from overheating, it must be ensured that the ambient temperature
does not exceed the maximum
temperature stated for the frequency converter
and that the 24-hour average temperature
is not exceeded
. Locate the
maximum temperature and 24-hour average in the paragraph
Derating for Ambient Temperature
.
If the ambient temperature is in the range of 45
°
C - 55
°
C, derating of the frequency converter will become relevant, see
Derating for Ambient Temperature
.
The service life of the frequency converter is reduced if derating for ambient temperature is not taken into account.
4.2.3 Field Mounting
For field mounting the IP 21/IP 4X top/TYPE 1 kits or IP 54/55 units are recommended.
4.2.4 Panel Through Mounting
A Panel Through Mount Kit is available for frequency converter series ADAP-KOOL Drive.
In order to increase heatsink cooling and reduce panel depth, the frequency converter may be mounted in a through panel.
Furthermore the in-built fan can then be removed.
The kit is available for enclosures A5 through C2.
NOTE
This kit cannot be used with cast front covers. No cover or IP21 plastic cover must be used instead.
Information on ordering numbers is found in the
Design Guide
, section
Ordering Numbers.
More detailed information is available in the
Panel Through Mount Kit instruction, MI.33.H1.YY,
where yy=language code.
Mechanical Installation
ADAP-KOOL
®
Drive Operating Instructions
24
MG.11.L4.02 - ADAP-KOOL
®
Drive
4
4